© 2022 WEINZIERL ENGINEERING GmbH
Seite 23/36
User control
The parameter “User control” determines the sending of telegrams on short and long button press:
▪
KNX standard: Long / Short
Long actuation:
Drive command via object 11
Short actuation:
Stop/Step command via object 12
Very long actuation:
Additional function
▪
KNX standard with turning time
Long actuation:
Drive command via object 11
Release after long actuation within turning time:
Stop/Step command via object 12
Release after long actuation after turning time:
No reaction
Short actuation:
Stop/Step command via object 12
Very long actuation:
Additional function
▪
KNX Inverted: Short / Long
Short actuation:
Drive command via object 11
Long actuation:
Stop/Step command via object 12
Actuation during drive:
Stop/Step command via object 12
Very long actuation:
Additional function
▪
Short / Short
Short actuation:
Drive command via object 11
Actuation during drive:
Stop/Step command via object12
Long actuation:
Additional function
▪
Short / Short plus Long with turning time
Short actuation:
Drive command via object 11
Long actuation:
Drive command via object 11
Release after long actuation within turning time:
Stop/Step command via object 12
Release after long actuation after turning time:
No reaction
Actuation during drive:
Stop/Step command via object 12
Very long actuation:
Additional function
▪
Hold (Deadman switch)
On actuation:
Drive command via object 11
On release:
Stop/Step command via object 12
▪
Hold with turning time
On actuation:
Drive command via object 11
On release within turning time:
Stop/Step command via object 12
On release after turning time:
No reaction