Part number 550-100-260/0520
23
ECO
®
Tec
G
AS
-
FIRED
WATER
BOILER
–
80/110/150/199
B
OILER
M
ANUAL
Venting & air — general
(continued)
&IGURE
Vent and air piping materials — Use only the materials listed below, ensuring that all materials meet
local codes (
see Figure 125, page 137 for part/kit numbers)
ALL
vent and air pipes require a
BIRD SCREEN at each termination
. Most kits do not include
the bird screens. Purchase bird screens separately from Weil-McLain or vent kit supplier if
not included. [Note — bird screening is integral to the 3" PVC Weil-McLain sidewall vent
cap, available for purchase from Weil-McLain. No additional screening is required.]
USE SWEEP ELBOWS FOR ALL VENT AND AIR PIPING
— DO NOT use short radius
elbows for vent or air piping. Boiler performance could be aff ected.
)TEM
-ATERIAL
3TANDARDSFORINSTALLATIONSIN
5NITED3TATES
#ANADA
(Note 2)
0LASTICPIPINGMATERIALS
6ENTORAIRPIPING
6ENT
PIPING
!IR
PIPING
6ENTORAIRPIPE
&
lTTINGS
PVC schedule 40 (Note 1)
ANSI/ASTM D1785
ULC S636
ABS,
PVC, PVC-DWV,
CPVC or
polypropylene
PVC-DWV schedule 40 (Note 1)
ANSI/ASTM D2665
N/A
CPVC schedule 40 (Note 1)
ANSI/ASTM F441
ULC S636
ABS-DWV schedule 40 (
Intake Only
)
ANSI/ASTM D2661
ULC S636
06#!"3PIPE
CEMENTPRIMER
PVC (Note 1)
ANSI/ASTM D2564/F656
ULC S636
Use only cement
and primer
suitable for piping
material used
CPVC (Note 1)
ANSI/ASTM F493
ULC S636
ABS schedule 40 (Note 1)
ANSI/ASTM D2235
ULC S636
0OLYPROPYLENE
VENTPIPElTTINGS
TERMINATIONSAND
CEMENT
3IMPSON$URAVENT
Obtain all materials from M&G
Simpson-Duravent
#ENTROTHERM%CO3YSTEMS)NNO&LUE
®
3INGLEWALL
Obtain all materials from Centrotherm
Note: See
page 137
for correct appliance adapters to be used.
See manufacturer’s literature for
detailed information
MUST USE LOCKING
COLLAR ON EVERY JOINT
ULC S636
PVC, PVC-DWV,
CPVC or
polypropylene
!,#STAINLESSSTEELPIPINGMATERIALS
6ENTPIPE
!,#
STAINLESS
STEEL
Heat Fab, Inc. — Saf-T-Vent
®
Z-Flex, Inc. — Z-Vent II
Dura-Vent — FasNSeal™
Metal-Fab, Inc. — CORR/GUARD
See Figure 125, page 137 for Mfg's adapter
part numbers.
Certifi ed for Category IV and
direct vent appliance venting
Certifi ed for Category IV and direct
vent appliance venting
7EIL-C,AINSTAINLESSSTEELBIRDSCREENSOR
(purchase separately) — see Figure 125, page 137 for part numbers.
Note 1:
Weil-McLain concentric vent kits are made from PVC
pipe and fi ttings.
Note 2:
System 636 PVC concentric terminations utilize PVC
pipe/fi ttings certifi ed to ULC S636.
If ULC S636 compliance is required, use only System 636
pipe, fi ttings and cement.
DO NOT mix piping from diff erent pipe manufacturers
unless using adapters specifi cally designed for the purpose
by the manufacturer.
Every joint on
polypropylene vent piping
must
include
a locking collar.
DO NOT use cellular core PVC (ASTM F891), cellular core
CPVC, or Radel
®
(polyphenolsulfone) in venting systems.
DO NOT cover non-metallic vent pipe and fi ttings with
thermal insulation.
ADAPTERS — The boiler comes with a 3" 3-in-
1 adapter as standard. This adapter allows the
installation of 3" PVC schedule 40, CPVC schedule
40, PVC-DWV schedule 40, AL29-4C stainless steel
(from Simpson-Duravent only) and Polypropylene
(from Simpson-Duravent & Centrotherm only)
piping without the need for extra adapters.
ADAPTERS – It may require additional adapters at the
terminations if using diff erent venting materials.
(When going from PP to the Weil-McLain side wall
plate, for example).
ADAPTERS - If using 2" piping, where approved for
the application, provide adapters for a 3" pipe
material (mentioned above) connections and at
the terminations, if required.