Venting — direct exhaust — termination
3e
17
Part Number
550-110-290/0219
CGt
GAS-FIRED WATER BOILER — Series 2 —
Boiler Manual
Figure 12 Vent termination
minimum clearances
1. Locate the boiler and vent penetration through the
wall so all requirements on this page and in
Figure
12 will be met. Also follow vent manufacturer’s
instructions.
2. Gases will form white plume in winter. Plume could
obstruct window view.
3. Prevailing winds could cause freezing of condensate
and water/ice buildup on vent termination, building,
plants or roof. Ice buildup on vent termination can
cause boiler shutdown and building freezeup.
4. Winds over 40 mph can cause nuisance boiler shut-
down if boiler is sidewall vented. This could result
in loss of heat to building, causing freezeup.
5. Locate or guard vent termination to prevent con-
densate from damaging exterior surfaces.
6. Locate the vent termination well away from trees,
shrubs, and decorative items.
7. Locate or guard vent to prevent accidental contact
by people or pets.
8. Do not terminate vent in window well, stairwell,
alcove, courtyard, or other recessed areas.
9. Do not wrap or insulate vent pipe or fittings.
10. Do not terminate vent above any door or window.
Condensate can freeze, causing ice formations.
11. Do not connect:
• Any other appliance to vent pipe.
• Multiple boilers to a common vent pipe.
12. Canadian installations — See B149.1 or B149.2
Installation Code. Terminate vent no less than 6
feet from another combustion air inlet, 3 feet from
any other building opening, and 3 feet from any gas
service regulator.
13. See
Figure
12
, showing that the vent must terminate:
• more than 4 feet below or to side of all doors
or windows.
• more than 1 foot above grade or anticipated
snow line.
• at least 7 feet above public walkway.
• 3 feet above any forced air intake within 10
feet.
14. Vent must also terminate:
• at least 6 feet away from adjacent walls.
• no closer than 5 feet below roof overhang.
• at least 4 feet horizontally (and in no case
above or below unless a 4 foot horizontal
distance is maintained) from electric meters,
gas meters, regulators, relief valves, and other
equipment.
15. Site conditions may dictate greater clearances.
16. Do not extend exposed vent pipe outside of building.
Condensate could freeze and block vent pipe.
A gas vent extending through an
exterior wall shall not terminate ad-
jacent to the wall or below building
extensions such as eaves, parapets,
balconies or decks. Failure to comply
could result in severe personal injury,
death or substantial property damage.
Follow instructions on this page when determining vent
location to avoid possibility of severe personal injury,
death or substantial property damage.