4 Module descriptions
| Technical Data
13
2484940000/00/02.2017
Manual UR67-Multiprotocol
Technical data
UR67-MP-xx-16DI-12-60M
(2426270000, 242630000)
UR67-MP-xx-16DO-12-60M
(2426280000, 2426310000)
UR67-MP-xx-8DIDO-12-60M
(2426290000, 2426320000)
Signal level of the outputs
–
Signal status “1”
–
min. (U
Aux
– 1 V)
min. (U
Aux
– 1 V)
Signal status “0”
–
max. 2 V
max. 2 V
Short-circuit-proof
–
Yes
Yes
Max. current-carrying capacity per mo-
dule
–
9.0 A (12 A
2)
)
9.0 A (12 A
2)
)
Overload-proof
–
Yes
Yes
Status indicator
–
Yellow LED (channel A),
white LED (channel B)
Yellow LED (channel A),
white LED (channel B)
Diagnosis indicator
–
Red LED, for each channel
Red LED, for each channel
Connection
–
M12 socket, 5-pole, A-coded
M12 socket, 5-pole, A-coded
Electronics/sensor power supply
Rated voltage U
S
24 V DC (SELV/PELV)
Voltage range
24 V DC ± 25%
Electronics current consumption
typically 60 mA
Sensor voltage
min. (U
System
– 1.5 V)
Sensor current consumption
max. 200 mA (at T
u
30°C)
Polarity protection
Yes
Status indicator (U
S
)
Green/red LED
Connection
7/8" plug and socket, 5-pole (UR67-MP-HP-X)
M12, 5-pole, L-coded (UR67-MP-78-X)
Actuator power supply
Rated voltage U
Aux
–
24 V DC (SELV/PELV)
Voltage range
–
24 V DC ± 25%
Potential isolation
–
Yes
Low voltage threshold
–
typically 17 V
Delay time for low voltage detection
–
typically 300 ms
Polarity protection
–
Yes
Actuator power supply indicator (U
Aux
)
–
Green/red LED
Connection
–
7/8" plug and socket, 5-pole (UR67-MP-HP-X) M12, 5-pole, L-coded (UR67-MP-78-X)
General data
Type of protection
IP 67 (only when all ports are either used or sealed)
Ambient temperature
-20°C to +70°C
Weight
500 g (UR67-MP-HP-X)
520 g (UR67-MP-78-X)
Enclosure material
Zinc diecast, nickel matt surface finish
Vibration resistance – vibration
15 g / 5–500 Hz
Vibration resistance – impact
50 g/11 ms
Tightening torques
M12 plug-in connector
0.5 Nm
1) In the case of inductive loads in utilisation category DC13 (in acc. with EN 60947-5-1), the outputs can operate with currents of 0.5 A and a frequency of 1 Hz.
2) Technically possible and approved on the following conditions: looped system/sensor power supply – max. 2.5 A; minimum cross-section of power supply wire –
5 x 1.0 mm²; max. ambient temperature – 40°C (104°F)