7 Commissioning
| Commissioning with PROFINET
30
2484940000/00/02.2017
Manual UR67-Multiprotocol
Selecting the controller version
▶
Double-click on the respective version, or use the mouse
to drag it to the second position in the table on the left-
hand side of the window.
The
Ethernet interface properties
window opens.
Ethernet interface properties
▶
Enter the designated IP address and the subnet mask for
the controller.
▶
Click on
New
.
The
New Industrial Ethernet subnet properties
window
opens.
▶
Enter a name for the subnet and confirm by clicking
OK
.
▶
Select the new subnet in the
Ethernet interface prop-
erties
window and confirm by clicking
OK
.
▶
Click on the network line in the configuration window.
▶
In the device catalogue, select the module under
PROFI-
NET IO/Additional field devices/ I/O /WI UR67
.
▶
Double-click on the module or drag it to the subnet line.
The module is added to the subnet.
Connecting the UR67-MP module
Viewing and changing device names
PROFINET devices are addressed in PROFINET via a unique
device name. These names can be freely assigned; however,
they can only be used once in the network.
▶
Double-click on the module.
The
Properties...
window opens.
Module properties
The device name must match the name that has
been assigned to the module.