WECO 5K3-XP-EMEA
51
2.9.1 Low Voltage LV HUB XP Dimensions
Weight:
Kg: 8
2.9.2 Control Logic and Protection Limit
The inverter, if applicable, must be set with the below restrictions in addition to the BMS control logic.
MAX CURRENT WITH BUS BAR
1.
The charge current will be limited to zero Amps when the single module voltage has been reached (56.8V).
2.
The discharge current will be limited to zero Amps when the single module voltage has been discharged to 50.4V.
3.
The battery system will communicate with the inverter to limit the current.
4.
Each Battery Module will be protected by the same logic separately as per single module protection concept.
5.
If some modules, individually, reach any fault status, the single module will protect and disconnect from the
system in less than 3 seconds.
6.
The current limit must be adjusted according to the real active batteries in system in order to restore the normal function.
7.
If the cluster is not balanced, the current limitation set from the HUB to the inverter will be sent in order to manage
the rest of active modules and clusters. At the same time, the imbalanced modules or cluster will equalize in
standby mode and will reconnect once in the normal range.
8.
If more than two batteries in one cluster are in protection mode, the entire cluster will protect by shutting down.
9.
If there are more than two clusters in protection mode, the full system will be protected.
10.
The battery sends information to the inverter to limit the charge/discharge current to zero Amps if the battery is
detecting an over current.
11.
The protection built into the BMS will automatically disconnect the battery when it detects excess values. The
BMS will attempt to reconnect up to three times to check if the excess values have returned to within the
permitted range. After three attempts to reconnect, the BMS will not attempt any further reconnections. The
Battery Module can be restarted using the module power switch and run button, however, if the external fault
condition which caused the Battery Module to shut down is not rectified, the battery will continue to enter the
shutdown mode.
12.
If the current of one cluster is larger than the current limit, the battery system will send a warning in accordance
with the single module BMS logic.
Modules Clusters
1
2
3
4
5
6
7
1
100
196
288
376
460
540
616
2
196
376
540
688
820
936
1036
3
288
540
756
936
1080
1188
1260
4
376
688
936
1120
1240
1296
1400
5
460
820
1080
1240
1300
1500
1750
6
540
936
1188
1296
1500
1800
2100
7
616
1036
1260
1400
1750
2100
2450
8
688
1120
1296
1600
2000
2400
2800
9
756
1188
1350
1800
2250
2700
3150
10
820
1240
1500
2000
2500
3000
3500
11
880
1276
1650
2200
2750
3300
3850
12
936
1296
1800
2400
3000
3600
4200
13
988
1300
1950
2600
3250
3900
4550
14
1036
1400
2100
2800
3500
4200
4900
15
1080
1500
2250
3000
3750
4500
5250