49
2.9 CAN HUB XP MODEL * ( compatible with 5K3 XP FW 60,02 and Above)
Multi Cluster Configuration
Required for installations of more than 1 cluster
5K3-XP LOW VOLTAGE HUB
SEE THE POWER/CURRENT CONFIGURATION
SET THE INVERTER POWER AS PER THE CABLES
’
CAPABILITIES
Each battery pack and each cluster must have the same Voltage and Firmware.
All stack configurations within 300Adc must use the WeCo Bus Bar
Each cluster must have the same number of batteries.
This BMS BMU Master Hub is mandatory when more than one cluster is connected on a
common bus bar.
The HUB works only with CAN communication approved inverters.
For HUB setting only use the WECO XP MANAGER SOFTWARE available on our download
area on