WECO 5K3-XP-EMEA
45
2.7.3 LV Direct Parallel Connection WITHOUT Certified Inverter BMS Communication (Open-Loop)
As per the Limited Performance Warranty document, a CAN communication between inverter and battery
is mandatory as per the Models listed in this manual.
Note that for installations
WITHOUT
certified Inverter BMS Communications, it Is not possible to
benefit of the performance warranty
The 5K3-XP Low Voltage Hub must not be used without Certified Inverter BMS Communication.
The
Low Voltage Hub must not be used without Certified Inverter BMS Communication. The LV HUB starts only with the
Inverter CAN HANDSHAKE message, thin imply the CAN BMS protocol in closed loop.
Performance Warranty is not applicable for non CAN-BMS connected batteries
LV/HV 5K3-XP
Individual Module Setting
Nominal DC Voltage
51.2
Nominal Amp Hours
105 / Usable 100Ah
Rated kWh Capacity
5.37 kWh
Standard Charge Current
(open Loop)
50 Adc
Max Charge Current
100A 110 Adc Peak
Standard Discharging Current
(open Loop)
50A Adc
Max Discharging Current
200 Adc Peak 5 sec before protection
Min Voltage (Open Loop)
50.5 Vdc
Max Voltage (Open Loop)
55.5 Vdc
Charging Current at Various Vdc at 77
°
F
(25
°
C)
From 50.5 Vdc up to 54.2 Vdc
50A (protection above 100A)
From 54.2 Vdc up to 55.5 Vdc
Max 10A
Operative Ambient Temperatures
Without CAN Communication
From +50
°
F to +95
°
F (+10
°
C to +35
°
C)
Max Cell Temp. +45
°
C Min Cell Temp +15
°
C
Operating Efficiency
Up to 98%
Self-Discharge Rate
1% self-discharge per month @ 77
°
F (25°C)
Memory Effect
None
Warranty Period
see Limited Warranty terms
Note
Without CAN communication, it is not always possible to perform a correct calibration of the cells due to the lack of interaction
with the inverter. It is therefore possible that the SoC 100% threshold is not reached.
It is recommended to use the minimum and maximum settings indicated, and to monitor the charging process to ensure that
the battery does not go into protection mode for Low or High Voltage, Temperature or Current.
Some inverter Logic or Battery protocol Logic could not allow the battery to reach the 0% in order to prevent the inverter shut
down * ( DC Powered)
Use conservative settings in order to respect the Limited Warranty Parameters and avoid damages to the battery, such
Overvoltage, Undervoltage, Over or Under Temperatures