WECO 5K3-XP-EMEA
16
SECTION 1 - STORAGE & PRE-OPERATIONAL PROCEDURES
1.1
Storage - Transportation
–
Removing / Relocation of Batteries
✓
This Battery is considered DANGEROUS GOODS by the United Nations and must be treated accordingly.
✓
Each box comes from the factory with the below labels:
✓
This battery can only be transported and stored with the original approved carton box, Certified as per UN
CLASS 9 Y80.
✓
This Battery must be stored in its original carton box in a dry and cool place. carton box is marked as below:
✓
The transportation and Storage State of Charge (SoC) shall not exceed 50%.
✓
The shelf period without recharging is 6 months, and then requires a quick charge up to 50% DoD. Charge at
0.1C and not more than 50% SOC. If shipped by sea, you must refer to the UN38.3 standard. If by road, refer
to local codes.
✓
To preserve the performance and shelf life, this battery should optimally be stored at 77°F /25°F and @70%
humidity.
✓
Acceptable storage temperature range of the battery is b59°F and +95°F /+15°C and +35°C
✓
The self-discharge in the range of +59°F to +119°F /+15°C to +35°C is around 1% a month. Anything outside
this range could exceed 10% a month.
✓
Do not store the batteries near sources of heat, vapor, gas, fuels, sparks or anything that could generate fire
or explosion.
✓
Store inside and protect from water and moisture.
✓
Transportation of new and used or damaged modules must be in accordance with the UN 38.3 Regulation and
with the Federal, State and Local regulations.
✓
If one or more working Battery Modules need to be removed or relocated, they must be marked as
USED
BATTERY
(follow local rules).
✓
If one or more Battery Modules need to be replaced due to damage, they should be marked as
DAMAGED
USED BATTERY
and follow any applicable procedures and all Federal, State and Local regulations.