10
Wayne Kerr AP 1kW Power Supplies • Issue 2
E.M.C.
Complies with EN50081-1 & EN50082-1 generic emissions and
immunity standards.
Note: This unit may exhibit deviance of up to 1% (CV mode) or 2% (CI
mode) in a 3V/m field.
Safety Standards
Designed to comply with BS4743/IEC348.
After Jan 1st 1997 all units will be compliant with EN61010-1.
Metering And Status
Twin 3 digit panel meters on front panel
Indication
12.5mm character height. High efficiency, red LED, digital display of
voltage and current output. Overvoltage limit (OVL trip point) can also
be displayed.
Twin bargraphs of 20 segments each give approximate indication of
voltage and current availability and will show trends.
Status flags give LED indication of CV and CI within panel meters.
Central status window indicates unregulated condition (UNREG),
overtemperature trip (OT), overvoltage limit (OVL). In addition, if the
IEEE488 bus option is fitted BUS indicates the unit is under bus control;
LSN indicates receiving data from the bus; TLK indicates transmitting
data on the bus; and SRQ indicates that a ‘service request’ has been
initiated
Meter Accuracy
Resolution & F.S.D
VOLTAGE
Accuracy at 23°C: ±0.2% rdg ±1 digit
Resolution: 100mV f.s.d 99.9V
CURRENT
Accuracy at 23°C: ±1% rdg ±1 digit
Resolution: 100mA f.s.d. 99.9A
IEEE (488) Interface
(When Fitted)
Refer to supplementary handbook (part no 9HAPHIBUS).
Float Voltage
These units are designed for either terminal to be floated up to 120V
d.c. from earth, including the output voltage.
The float sources must
be impulse free
(see IEC 664) i.e. do not float the output on an
unisolated a.c. supply.
Environmental
Operating temperature 0-40°C
Storage temperature -20 to +60°C
Cooling: Fan cooled. Air intake on front panel.
Overtemperature trip protection is featured.
RH <80% Non-condensing
Altitude <2000m
Pollution degree 2 - Normally non-conductive pollution.
Non-corrosive, non-explosive atmosphere.
Installation category 2 - Connected via a plug and socket to the supply.
For indoor use only.
Содержание AP10030
Страница 63: ...AP 1kW Power Supplies Issue 2 Circuit Diagrams Page 63...
Страница 64: ...AP 1kW Power Supplies Issue 2 Circuit Diagrams Page 64...
Страница 65: ...AP 1kW Power Supplies Issue 2 Circuit Diagrams Page 65...
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......