INITIAL STARTUP PROCEDURE
3. Initial/Limit Setup
The first time the controller is powered on, you must first set the limits. The LED screen will flash with the error E17, and you must reset
the limits. This will also occur whenever the position sensor is disconnected from the controller. The position sensor, photoeyes, sensing edge, and interlock
switch must be connected before the limits can be set. If, for any reason, the limits cannot be set, please refer to troubleshooting section 8.
A. To enter the Menu, press and hold the OPEN, STOP, CLOSE membrane buttons for 3 seconds. A count down timer on the top left corner of the LED
screen will display the remaining time left to hold. Refer to
Fig 6-A
for the complete menu structure.
B. Holding the Stop button for 1 second will go back up a level in the Menu. Continuing to hold the STOP button will continue to go back up the menu
structure until the main screen.
C. Once in the main screen, a 25 second countdown timer will show on the upper left hand corner. This countdown timer displays how long until the
OPEN/STOP/CLOSE buttons will no longer give access to the MENU. Once inside the menu, use the
OPEN button to scroll up, STOP button to enter,
and
CLOSE to scroll down.
Pressing OPEN/STOP/CLOSE immediatly exits the counter.
Note: Instead of using the front panel buttons one can access the menu from the control unit using menu/enter, the
▲,
and
▼
buttons.
1. Enter the Menus
2. Scroll down until you reach the LIMIT SETUP and hit enter.
3. Scroll down and enter into Quick Setup. A code request screen will appear. Enter the 3 digit passcode to gain access by scrolling up or down.
Your passcode is located on a seperate addendum.
NOTE:
Do not
display or freely give out the passcode.
4. Follow the prompts in order to set the open and close limits on the door. During this time, use the OPEN, CLOSE buttons to move the
door. Again, the STOP button will be used as the ENTER function. If no error has occurred, it will then display QUICK SETUP DONE, otherwise if
failed; QUICK SETUP ABORTED and it must be redone. Refer to Trouble shooting section 8 if required.
NOTE: When setting the position, the position sensor count will be displayed. Verify the encoder count increases when the door is moving in the up
direction, and does not roll over to the negative position.
4. Verification
Test each sensor to make sure the controller recognizes the fault.
A. Photoeyes -Obstruct the beam with a sold object. Photoeye should reverse door direction.
B. Sensing Edge -Place a solid object, taller than 12”, on the floor and close the door. Sensing edge should reverse door direction on contact
with object.
C. Interlock Switch -This is a constant activation sensor, release the hand crank from the switch, the door should stop and a fault display
NOTE: all faults and sensor activations are logged into the Fault Log. Access this through the menu SYSTEM STATUS > FAULT LOG
in the Controller Menu. To clear faults hold the STOP button for 1 second once the fault has been fixed.
MENUS
1. Express Menu
The Express Menu is accessed by scrolling up, when at the idle screen or after exiting the menus. The express menu contains display options,
timers, settings reset, and the emergency JOG. The timer functions in the Express Menu are shortcuts to timers in the system configuration menu without the
need of a passcode.