wattstopper CI-300 Скачать руководство пользователя страница 9

SENSOR ADJUSTMENT

The sensors are factory preset to allow for quick installation in most applications. 

Verification of proper wiring or coverage, or customizing the sensor’s settings can 

be done using the following procedures. To make adjustments, open the Front Cover 

with a small screwdriver.

There is a 30 second 

warm-up period when 

power is first applied.

 

Before making 

adjustments, make 

sure the office furniture 

is installed, lighting 

circuits are turned on, 

and the HVAC systems 

are in the overridden/on 

position. VAV systems 

should be set to their 

highest airflow. Set the 

DIP switches to the 

desired settings. See 

“DIP Switch Setting”, 

next page.

To Test Occupancy Sensors

1.   Ensure the PIR Activity LED is enabled (DIP switch 6 ON) and PIR Sensitivity is 

set to MAX (DIP switch 7 ON).

2.  Ensure the Time Delay is set for 

Test Mode*

 using the “5 seconds/SmartSet” 

setting. (DIP switches 3,4, & 5 are OFF). 

3.   Ensure that the Light Level is at default (maximum). See the Light Level Feature 

section of this document for instructions.

4.   Remain still. The green LED should not flash. The lights should turn off after 5 

seconds. (If not, see “Troubleshooting.”)

5.   Move about the coverage area. The lights should come on. 

When testing and adjustment is complete, reset DIP Switches and Light Level to the 

desired settings, and replace the cover on the sensor.

If you need to invoke the 

Test Mode

 and the DIP switches are already set for 

5 seconds/SmartSet, toggle DIP switch #5 ON then back to the OFF position. This 

provides a 5 minute test period. During the test period, the Time Delay is only 5 

seconds.

Keyhole slots
(for mounting to 
4" octagonal box)

Double gang 
mudring
mounting holes 

Light level 
pushbutton

DIP 
switches

PIR lens

ON

1

2

3

4

5

6

7

ECE

PIR Activity
LED (Green)

Visit our website for FAQs: www.wattstopper.com

Содержание CI-300

Страница 1: ...r Packs Isolated Relay Rating 1A 30VDC VAC Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if n...

Страница 2: ...half wave rectified AC CI 300 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS COVERAGE PATTERN The CI 300 provides a 360 coverage...

Страница 3: ...ions At heights of more than 12 14 feet you may start to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a...

Страница 4: ...nal on sensor Wiring ONE LIGHTING LOAD FOR OCCUPANCY CONTROL AND A SECOND LOAD FOR OCCUPANCY AND LIGHT LEVEL AMBIENT LIGHT CONTROL connect BLUE wire from power pack to Control Out terminal on sensor B...

Страница 5: ...es White Black Red Line Voltage Wire Color Legend Wiring the ISOLATED RELAY The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requires this output Relay...

Страница 6: ...ips 2 Blue Control Out Black 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 300 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch...

Страница 7: ...ght Level pushbutton See Sensor Adjustment 2 Momentarily press the Light Level pushbutton Do not exceed 4 seconds The sensor enters setup mode as indicated by the rapidly flashing green LED The LED wi...

Страница 8: ...ensor securely in place 6 Snap the front cover onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low v...

Страница 9: ...Time Delay is set for Test Mode using the 5 seconds SmartSet setting DIP switches 3 4 5 are OFF 3 Ensure that the Light Level is at default maximum See the Light Level Feature section of this document...

Страница 10: ...thin the 30 second re trigger period Automatic On This mode uses occupancy as well as switch activation to turn the load ON A manual switch provides the following additional functionality a The load c...

Страница 11: ...using SmartSet or you can select a fixed time delay SmartSet records occupancy patterns and uses this history to choose an optimal time delay from 5 to 30 minutes SmartSet behavior starts immediately...

Страница 12: ...that high voltage is present to power pack If it is replace power pack PIR Activity LED flashes 1 If the sensor s Light Level feature has been turned on the lights connected to the Light Level Output...

Страница 13: ...lay to minimum and allow the sensor to time out If the lights turn off the sensor is working properly see Sensor Adjustment for readjustment of sensor Unwanted Sensor Activations LED flashes Possible...

Страница 14: ...120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and work...

Отзывы: