wattstopper CI-300 Скачать руководство пользователя страница 8

Call 800.879.8585 for Technical Support

Rear
housing

Depluggable terminal

Front
cover

Ceiling

Spring clips (2)

MOUNTING THE SENSOR

Directly to Ceiling

1.  Attach the plastic spring clips to 

the edge of the sensor in the slots 

provided.

2.  Cut a 3.5” to 4” round hole in 

the acoustic ceiling tile at the 

mounting location. A 3.5” hole is 

recommended for a secure fit.

3.  Pull the low voltage wire from the 

power pack to the sensor through 

the hole.

4.  Connect the low voltage wires to 

the appropriate terminals on the 

sensor.

5.  Push the sensor up through the 

hole until the Spring Clips hold the 

sensor securely in place.

6.  Snap the front cover onto the 

sensor.

Using an Octagonal J-Box

1.  Pull the low voltage wires from the 

power pack into the J-Box through the 

conduit knockout.

2.  Connect the low voltage wires to the 

appropriate terminals on the sensor.

3.  Loosen the appliance mounting screws 

attached to the J-Box

4.  Align the sensor in the J-Box so that 

the mounting screws on the box match 

the key holes on the sensor’s rear 

housing.

5.  Push the sensor up into the J -Box and 

twist it so that the mounting screws are 

seated in the keyhole slots.

6.  Tighten the two screws to secure the sensor to the J-Box.
7.  Snap the front cover onto the sensor.

Ceiling Mount

Ceiling Mount

J-Box Mount

Rear
Housing

Depluggable
Terminal

4" Octagonal J-Box 
(at least 1.5" deep)

Front
Cover

Ceiling

Screws

Содержание CI-300

Страница 1: ...r Packs Isolated Relay Rating 1A 30VDC VAC Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if n...

Страница 2: ...half wave rectified AC CI 300 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS COVERAGE PATTERN The CI 300 provides a 360 coverage...

Страница 3: ...ions At heights of more than 12 14 feet you may start to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a...

Страница 4: ...nal on sensor Wiring ONE LIGHTING LOAD FOR OCCUPANCY CONTROL AND A SECOND LOAD FOR OCCUPANCY AND LIGHT LEVEL AMBIENT LIGHT CONTROL connect BLUE wire from power pack to Control Out terminal on sensor B...

Страница 5: ...es White Black Red Line Voltage Wire Color Legend Wiring the ISOLATED RELAY The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requires this output Relay...

Страница 6: ...ips 2 Blue Control Out Black 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 300 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch...

Страница 7: ...ght Level pushbutton See Sensor Adjustment 2 Momentarily press the Light Level pushbutton Do not exceed 4 seconds The sensor enters setup mode as indicated by the rapidly flashing green LED The LED wi...

Страница 8: ...ensor securely in place 6 Snap the front cover onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low v...

Страница 9: ...Time Delay is set for Test Mode using the 5 seconds SmartSet setting DIP switches 3 4 5 are OFF 3 Ensure that the Light Level is at default maximum See the Light Level Feature section of this document...

Страница 10: ...thin the 30 second re trigger period Automatic On This mode uses occupancy as well as switch activation to turn the load ON A manual switch provides the following additional functionality a The load c...

Страница 11: ...using SmartSet or you can select a fixed time delay SmartSet records occupancy patterns and uses this history to choose an optimal time delay from 5 to 30 minutes SmartSet behavior starts immediately...

Страница 12: ...that high voltage is present to power pack If it is replace power pack PIR Activity LED flashes 1 If the sensor s Light Level feature has been turned on the lights connected to the Light Level Output...

Страница 13: ...lay to minimum and allow the sensor to time out If the lights turn off the sensor is working properly see Sensor Adjustment for readjustment of sensor Unwanted Sensor Activations LED flashes Possible...

Страница 14: ...120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and work...

Отзывы: