wattstopper CI-300 Скачать руководство пользователя страница 11

Visit our website for FAQs: www.wattstopper.com

Override: Switch 2

To override all sensor functions, set DIP switch 2 to the ON position. The green LED 

will come on and stay on for the duration of the override.
This bypasses the light level and occupancy detection control functions of the 

sensor, but still allows the lights to be manually controlled with a light switch, if one 

is installed.

Time Delay: Switches 3, 4, 5

The sensor will hold the lights on as long as occupancy is detected. The time delay 

countdown starts when no motion is detected. After no motion is detected for the 

length of the time delay, the sensor will turn the lights off. The sensor can select the 

time delay using SmartSet, or you can select a fixed time delay.

•  SmartSet records occupancy patterns and uses this history to choose an optimal 

time delay from 5 to 30 minutes. SmartSet behavior starts immediately and is 

refined continually as history is collected.

Walk-through mode turns the lights off three minutes after the area is initially 

occupied, if no motion is detected after the first 30 seconds. If motion continues 

beyond the first 30 seconds, the selected time delay applies. 

LED: Switch 6

When enabled, the green PIR Activity LED under the sensor lens will light when the 

sensor detects motion.

Sensitivity: Switch 7

Minimum forces a reduced detection range for the PIR.
Max/SmartSet causes the sensor to monitor the controlled area and automatically 

select the maximum sensitivity that will provide reliable operation without false 

detection. This setting is constantly updated.

Содержание CI-300

Страница 1: ...r Packs Isolated Relay Rating 1A 30VDC VAC Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if n...

Страница 2: ...half wave rectified AC CI 300 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS COVERAGE PATTERN The CI 300 provides a 360 coverage...

Страница 3: ...ions At heights of more than 12 14 feet you may start to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a...

Страница 4: ...nal on sensor Wiring ONE LIGHTING LOAD FOR OCCUPANCY CONTROL AND A SECOND LOAD FOR OCCUPANCY AND LIGHT LEVEL AMBIENT LIGHT CONTROL connect BLUE wire from power pack to Control Out terminal on sensor B...

Страница 5: ...es White Black Red Line Voltage Wire Color Legend Wiring the ISOLATED RELAY The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requires this output Relay...

Страница 6: ...ips 2 Blue Control Out Black 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 300 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch...

Страница 7: ...ght Level pushbutton See Sensor Adjustment 2 Momentarily press the Light Level pushbutton Do not exceed 4 seconds The sensor enters setup mode as indicated by the rapidly flashing green LED The LED wi...

Страница 8: ...ensor securely in place 6 Snap the front cover onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low v...

Страница 9: ...Time Delay is set for Test Mode using the 5 seconds SmartSet setting DIP switches 3 4 5 are OFF 3 Ensure that the Light Level is at default maximum See the Light Level Feature section of this document...

Страница 10: ...thin the 30 second re trigger period Automatic On This mode uses occupancy as well as switch activation to turn the load ON A manual switch provides the following additional functionality a The load c...

Страница 11: ...using SmartSet or you can select a fixed time delay SmartSet records occupancy patterns and uses this history to choose an optimal time delay from 5 to 30 minutes SmartSet behavior starts immediately...

Страница 12: ...that high voltage is present to power pack If it is replace power pack PIR Activity LED flashes 1 If the sensor s Light Level feature has been turned on the lights connected to the Light Level Output...

Страница 13: ...lay to minimum and allow the sensor to time out If the lights turn off the sensor is working properly see Sensor Adjustment for readjustment of sensor Unwanted Sensor Activations LED flashes Possible...

Страница 14: ...120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and work...

Отзывы: