TROUBLESHOOTING

CAUTION

TURN POWER OFF AT THE CIRCUIT BREAKER 

 

BEFORE WORKING WITH OR NEAR HIGH VOLTAGE.

Lights do not turn on with occupancy, and the following condition exists:

•  PIR Activity LED does not flash:

NOTE: When power is initially applied to the sensor, there is a warm-

up period of up to 30 seconds before the LED is active.

1.  Check that the circuit breaker has been turned back on.
2.  Make sure that the PIR Sensitivity is set for Max/Smartset (DIP switch 7 on).
3.  Check all sensor and power pack wire connections.
4.   Check for 24V input to the sensor.  

If 24V is present, replace the sensor. 

 If 24V is not present, check that high voltage is present to power pack.  

If it is, replace power pack.

•  PIR Activity LED flashes:

1.   If the sensor’s Light Level feature has been turned on, the lights connected 

to the Light Level Output might be held off because of the level of ambient 

light in the controlled area. To test whether the Light Level adjustment is 

the problem, cover the PIR lens and PIR Activity LED (see diagram) with your 

hand to see if the lights turn on. If the lights turn on, the Light Level setting 

was keeping the lights off (see, “Sensor Adjustment” for readjustment).

2.  Check all sensor and power pack wire connections.
3.   Check for 24VDC at the power pack’s blue wire connection to 

sensor while sensor is activated. If there is no voltage, replace 

the sensor. If there is voltage, replace the power pack.

Call 800.879.8585 for Technical Support

Содержание CI-300

Страница 1: ...r Packs Isolated Relay Rating 1A 30VDC VAC Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if n...

Страница 2: ...half wave rectified AC CI 300 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS COVERAGE PATTERN The CI 300 provides a 360 coverage...

Страница 3: ...ions At heights of more than 12 14 feet you may start to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a...

Страница 4: ...nal on sensor Wiring ONE LIGHTING LOAD FOR OCCUPANCY CONTROL AND A SECOND LOAD FOR OCCUPANCY AND LIGHT LEVEL AMBIENT LIGHT CONTROL connect BLUE wire from power pack to Control Out terminal on sensor B...

Страница 5: ...es White Black Red Line Voltage Wire Color Legend Wiring the ISOLATED RELAY The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requires this output Relay...

Страница 6: ...ips 2 Blue Control Out Black 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 300 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch...

Страница 7: ...ght Level pushbutton See Sensor Adjustment 2 Momentarily press the Light Level pushbutton Do not exceed 4 seconds The sensor enters setup mode as indicated by the rapidly flashing green LED The LED wi...

Страница 8: ...ensor securely in place 6 Snap the front cover onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low v...

Страница 9: ...Time Delay is set for Test Mode using the 5 seconds SmartSet setting DIP switches 3 4 5 are OFF 3 Ensure that the Light Level is at default maximum See the Light Level Feature section of this document...

Страница 10: ...thin the 30 second re trigger period Automatic On This mode uses occupancy as well as switch activation to turn the load ON A manual switch provides the following additional functionality a The load c...

Страница 11: ...using SmartSet or you can select a fixed time delay SmartSet records occupancy patterns and uses this history to choose an optimal time delay from 5 to 30 minutes SmartSet behavior starts immediately...

Страница 12: ...that high voltage is present to power pack If it is replace power pack PIR Activity LED flashes 1 If the sensor s Light Level feature has been turned on the lights connected to the Light Level Output...

Страница 13: ...lay to minimum and allow the sensor to time out If the lights turn off the sensor is working properly see Sensor Adjustment for readjustment of sensor Unwanted Sensor Activations LED flashes Possible...

Страница 14: ...120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and work...

Отзывы: