WIRING DIRECTIONS
CAUTION
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING POWER PACKS OR SENSORS.
Each Watt Stopper BZ series power pack
can supply power for 8 CI-300 sensors.
When using more sensors than this,
multiple power packs are required.
Refer to the wiring diagram on the next
page for the following procedures:
Connect the
low voltage
:
• RED wire (+24VDC) from power pack to
the +
24V
terminal on the sensor.
• BLACK wire (Return) from power pack
to
Common
terminal on the sensor.
Wiring a
SINGLE LIGHTING LOAD
CONTROLLED BY OCCUPANCY
–connect:
• BLUE wire from power pack to Control Out terminal on sensor.
Wiring a
SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY, DEPENDENT ON
LIGHT LEVEL (AMBIENT LIGHT)
–connect:
• BLUE wire from power pack to Light Level terminal on sensor.
Wiring
ONE LIGHTING LOAD FOR OCCUPANCY CONTROL, AND A SECOND LOAD
FOR OCCUPANCY AND LIGHT LEVEL (AMBIENT LIGHT) CONTROL
–connect:
• BLUE wire from power pack to Control Out terminal on sensor.
• BLUE wire from Auxiliary Relay pack to Light Level terminal on sensor.
• BLACK wire from Auxiliary Relay pack to Common terminal on sensor.
To add a
MANUAL SWITCH
such as the LVS-1 Momentary Toggle Switch, or RS2-3
Low Voltage Momentary Switch to the above applications–connect:
• Wire from one side of switch to Common terminal on sensor.
• Wire from other side of switch to Man Switch terminal on sensor.
Call 800.879.8585 for Technical Support
CI-300
Passive Infrared
Occupancy Sensor
U.S.Patents:
5,124,566
5,640,113
Patent Pending
+24VDC/VAC
Connect to Watt Stopper
Class 2 Power Packs
For Indoor Use Only
Model#:
03079r2
LISTED
88T9
Appliance
Control
Santa Clara, CA
800.879.8585
Relay Com.
N.O.
N.C.
Control Out.
Man. Switch
+24V
Common
Light Level
Wiring
terminals