Inverter Display Abbreviation and Complete Name Reference Table
Abbreviation Complete Name
Safety Set
Battery_ID Set
Work Mode
Export Limit
Feed in Grid
Reactive Modes
PF
Qt
Q(P)
Q(U)
Fixed Q
On-Off Grid SW
Relax OffGrid
Offgrid ReConn.
Load Shifting
SetMaxGrid
OnGrid SocProt.
OnGrid EndSOC
OffGrid SocProt.
OffGrid EndSOC
Unbalan. Output
System Maint.
Multi-INV Role
SOC Reset
MPPT Parallel
Select the code that meet local regulatory requirements
Select the battery model
Current work mode / work mode setting
On-grid export limit function switch
Set the percentage of the power that is allowed to feed to the grid
Reactive Power Mode
"Under ""Reactive Mode" "The reactive power can be regulated by the
parameter PF (Power Factor)."
"Under ""Reactive Mode" "The reactive power can be regulated by the
parameter Q-Var limits (in %)."
"Under ""Reactive Mode" "The PF changes with the output power of the
inverter."
"Under ""Reactive Mode" "The reactive power changes with the grid voltage"
The reactive power ratio when the "Reactive Mode" is Qt.
Off-grid function switch (If turn it on, the inverter will automatically switch
to off-grid mode to ensure the back-up side power supply when the gird is
abnormal or off, otherwise, there is no output on the back-up side)
Reduce the switching sensitivity of the On/Off-grid (applied to the places
where the grid is unstable or inverter always entered off-grid mode for some
reasons)
When the power grid is off, the inverter can automatically restart the back-up
output after a fault or overloading protection occurred if the Off-grid restart
is ON. Otherwise, the back-up output needs to be restarted manually
Peakload shifting function switch
Set max allowed power from grid (under the condition of Peakload Shifting is
on)
On-grid battery SOC (State of Charge) Protection
End-of-discharge SOC of on-grid
Off-grid SOC Protection
End-of-discharge SOC of off-grid
3-Phase Unbalanced Output Switch when inverter work on On-grid state
System maintenance, includes inverter stop and run, system restart
In the multi-inverter parallel system, set the role of one inverter as the master
and the other inverter as the slave.
If turned it on, the battery will be automatically charged to calibrate the
battery SOC. After the battery is charged, this function will be turned off
automatically .
If MPPT is connected in parallel, enable this function.