User Manual
46
4.4.2 Installing the AC connector
4)
Insert the cable into the rubber core according to the line sequence
,
observe the perspective hole
,
the cable is in place
,
and the torque of the crimping screwdriver is 5 ± 0.1N.m.
3) Thread the stripped wire into the lock nut and the main body (the multi-core, multi-strand copper wire cable must be
riveted to the cord end terminal).
15mm
95-100mm
2) According to the figure below select an appropriate cable, peel the insulation sleeve of the AC cable off for 95-
100mm, and peel off the end of 3L /PE / N wires for 15mm.
The AC terminal block is on the bottom side of the inverter.
1) Seal accessory option.
The recommended outer diameter of the cable is 20-24 mm and 24.5-30mm.
If the outer diameter of the cable is greater than 24mm, remove part 1.
Part 1
Part 2
Danger
:
High voltage may be present in the inverter!
Ensure all cables are voltage-free before electrical connection.
Do not connect the AC circuit breaker until all inverter electrical connections are completed.