DSBA3401 · Rév. 08/08/2020
51
EN
POSI-BBPR (GPS) : description
The GPS version includes BBPR and positioning function
.
Battery position backup:
This system insure a return to predefined position in case of power failure. The predefined position can be set close
(default) or open
.
Positioning:
0-10 V:
In case of outside event, absence of control signal (accidental wires cut for example) but in the presence of power,
the actuator will travel to defined position (open or closed valve). As standard our actuators will close themselves with absence
of control signal but there are other possibilities on request.
4-20 mA:
In case of outside event, absence of setpoint signal (accidental wires cut for example) but in presence of power, the
actuator will stay in its position
Actuator voltage
Battery voltage
24 V DC
Charging status feedback relay (65/66)
24 V DC - 1 A max
Battery capacity
600 mAh
Failure feedback relay (67/68)
24 V DC - 3 A max
Charging current
180 mA
Temperature
-10 °C à +40 °C
Maximum battery charge duration
3,5 h
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 06 ATEX 6006X
Ambient temperature: -10 °C to +40 °C
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
20 V to 30 V AC 50/60 Hz and 20 V to 48 V DC
C2
C4
LED
B1
B2
B3
C3
C1
C5
J1
C6
C7
C8
Rep Terminals Description
B1
« Close » button
B2
« Mem» button
B3
« Open » button
C1 A,C
Motor
connector
C2
67,68
Failure feedback relay
C3
65,66
Charging status feedback relay
C4
F (+)
F (-)
T (+)
Battery connector
C5
17 (-)
18 (+)
power supply connector
C6
15(-)
16(+)
Positioning setpoint signal con-
nector (0-10 V or 4-20 mA)
C7
13A(+)
13B(+)
14(-)
Positioning feedback signal
connector.
13A=0-10 V et 13B=4-20 mA
C8 A,0,B
RS485
connector
J1 CV1
Bluetooth
®
activation jumper
LED Description
MANU manual / Bluetooth
®
functioning mode
ERROR
Error detected:
Timestamp memory empty/scheduler selected
Clock failure
Excessive temperature
Excessive torque
HORO Weekly scheduler functioning mode
ACT
Power supply:
Slow blinking (1 s) : charged battery
Rapid blinking (0.5 s) : battery charging
APPR Learning mode selected
APPR1 Open position stored (confirmation)
POSI Positioning
mode
APPR2 Closed position stored (confirmation)
The factory default configuration is "normally closed"