DSBA3401
·
Rév. 08/08/2020
40
EN
N
-
Open
Close
Ph
+
Modulating 3-point control
POWER SUPPLY AND CONTROL
TP/PE
9
8
FCF
FC0
A
B
+
—
~
~
FC2
FC1
A
3
2
1
100V-240V 50/60Hz
(100V-350V DC)
15V-30V 50/60Hz
(12V-48V DC)
C
M
N
-
Open
Ph
+
On-off control
FEEDBACK
18
17
TP/PE
3
2
1
3
2
1
TP/PE
CO
MM
O
N
F
C
1
CO
MM
O
N
F
C
2
FEEDBACK FC
1
FEEDBACK FC
2
4
5
6
7
D2
D1
Part
Description
Part
Description
FC0
Open limit switch
FC1
Auxiliary limit switch 1
FCF
Close limit switch
FC2
Auxiliary limit switch 2
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 06 ATEX 6006X
Ambient temperature: -20 °C to +70 °C
Schéma électrique multivolt (modèles standard)
4,5
Auxiliary limit switch 1 NO
1,2,3,4
Power supply terminal
6,7
Auxiliary limit switch 2 NO
D1/D2
Failure report Terminal (24V DC / 3A max)
4,8
Auxiliary limit switch 1 NC
6,9
Auxiliary limit switch 2 NC