DSBA3401
·
Rév. 08/08/2020
48
EN
BBPR (GS6) : description
Actuators with emergency unit (on-off wiring mandatory)
The BBPR models include an emergency battery unit controled by an electronic board. This system insure a return to predefi-
ned position in case of power failure. The predefined position can be set close (default) or open.
REP TERMINAL DESCRIPTION
C1
17 (-)
18 (+)
power supply connector
C2
F (+)
F (-)
T (+)
Battery unit connector
C3
A
B
C
Motor connector
C4
1)
D3
D4
Failure feedback connector
C5
1)
65
66
Charging feedback connector
C6
A
0
B
RS485 connector
J1 Bluetooth
®
activation jumper
1) The auxiliary cables must be connected to inside instal-
lation only
LED
DESCRIPTION
ACT
Power supply:
Slow blinking (1 s) : charged battery
Rapid blinking (0.5 s) : battery charging
ERROR
Error detected:
Timestamp memory empty/scheduler selected
Clock failure
Excessive temperature
Excessive torque
HORO Weekly scheduler functioning mode
MANU manual / Bluetooth
®
functioning mode
WIRE Electric
wiring
mode
C1
C2
C5
C6
J1
C3
C4
LED
Actuator voltage
Battery voltage
24 V DC
Charging status feedback relay (65/66)
24 V DC - 1 A max
Battery capacity
600 mAh
Failure feedback relay (D3/D4)
24 V DC - 3 A max
Charging current
180 mA
Temperature
-10 °C to +40 °C
battery charge maximum duration 3,5 h
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 06 ATEX 6006X
Ambient temperature: -10 °C to +40 °C
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
20 V to 30 V AC 50/60 Hz and 20 V to 48 V DC
The BBPR actuators can be only on-off mode wired.
Following a power failure,
the BBPR unit will reset
after 4 minutes
The factory default configuration is "normally closed"