Lync WQ-RS
SECTION 6: APPENDIX
L- OMM-005_A
•
2/23/2022
Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
33
of
34
6.
Appendix
The following tables are intended as a guide to determining the flow rates for the WQ-RS series
RO systems. All flows are in gallons per minute (GPM). Nominal flows for systems with reject
recycle and a feed water Silt Density Index less than 3.
MODEL NUMBER
WQ-RS-005-R
WQ-RS-010-R
WQ-RS-015-R
Product
2.5
5
7.5
Reject
2.5
1.7
2.5
Reject Recycle
3.6
3.3
2.1
Nominal flows for systems with reject recycle and a feed water Silt Density Index of 3 to less than 5.
MODEL NUMBER
WQ-RS-005-R
WQ-RS-010-R
WQ-RS-015-R
Product
2.3
4.3
6.3
Reject
2.3
1.4
2.1
Reject Recycle
4.3
3.9
2.3
Temperature Correction Factors
°C
°F
CORRECTION FACTOR
30
86
1.16
29
84.2
1.13
28
82.4
1.09
27
80.6
1.06
26
78.8
1.03
25
77
1.00
24
75.2
0.97
23
73.4
0.94
22
71.6
0.92
21
69.8
0.89
20
68
0.86
19
66.2
0.84
18
64.4
0.81
17
62.6
0.79
16
60.8
0.77
15
59
0.74
14
57.2
0.72
13
55.4
0.70
12
53.6
0.68
11
51.8
0.66
10
50
0.64
9
48.2
0.62
8
46.4
0.61
7
44.6
0.59
6
42.8
0.57
5
41
0.55
Multiply the nominal product flow at 25° C by the temperature correction factor to determine the
flow at various other temperatures.