MOTOR TROUBLE SHOOTING CHART

 

TROUBLE 

CAUSE 

WHAT TO DO 

Motor fails to start  Blown fuses 

Replace fuses with proper type and rating. 

Overload trips 

Check and rest overload in starter. 

Improper power supply 

Check to see that power supplied agrees 
with motor nameplate and load factor. 

Open circuit in winding or control 
switch 

Indicated by humming sound when switch is 
closed. 

Mechanical failure 

Check to see if 
motor and drive 
turn freely. Check 
bearing and 
lubrication. 

Short circuited stator 

Indicated by blown fuses. Motor must be 
rewound. 

Poor stator coil connection 

Remove end bells, locate with test lamp. 

Rotor defective 

Look for broken bars or end ring. 

Motor may be overloaded 

Reduce load. 

Motor Stalls 

One phase connection 

Check lines for open phase. 

Wrong application 

Change type or size. Consult manufacturer. 

Overload motor 

Reduce load. 

Low motor voltage 

See that nameplate 
voltage is 
maintained. Check 
connection. 

Open circuit 

Fuses blown, check overload relay, stator 
and push buttons. 

Motor runs and 
then dies down 

Power failure 

Check for loose connections to line, to fuses 
and to control. 

Motor does not 
come up to speed 

Not applied properly 

Consult supplier for proper type. 

Voltage too low at motor terminals 
because of line drop. 

Use higher voltage on transformer 
terminals or reduce load. Check 
connections. Check conductors for 
proper size. 

Broken rotor bars or loose rotor. 

Look for cracks near the rings. A new 
rotor may be required as repairs are 
usually temporary. 

Motor takes too 
long to accelerate 

Open primary circuit 

Locate fault with testing device and repair. 

Excess loading 

Reduce load. 

Poor circuit 

Check for high resistance. 

Defective squirrel cage rotor 

Replace with new rotor. 

Applied voltage too low 

Get power company to increase power tap. 

Wrong rotation 

Wrong sequence of phases 

Reverse connections at motor or at 
switchboard. 

Motor overheats 
while running under 
load 

Overloaded 

Reduce load. 

Frame or bracket vents may be 
clogged with dirt and prevent 
proper ventilation of motor. 

Open vent holes and check for a continuous 
stream of air from the motor. 

Содержание Lync WQ-RS

Страница 1: ...ubject to change without notice from Lync a division of Watts Water Technologies Inc Lync makes no warranty of any kind with respect to this material including but not limited to implied warranties of...

Страница 2: ...1 1 Specifications 4 1 2 RO Overview 4 1 3 Pretreatment 5 2 CONTROLS INDICATORS AND COMPONENTS 7 2 1 System Components 7 2 2 Controller Drawing 8 3 OPERATION 10 3 1 Installation 10 3 2 Plumbing Conne...

Страница 3: ...d be conducted prior to the initial sizing and selection of this system NOTES Changes in operating variables are beyond the control of Lync The end user is responsible for the safe operation of this e...

Страница 4: ...ilable 230 VAC 3 phase 60 Hz 15 amps other voltages available TEFC Motor horse power 5 Dimensions L x W x H inches 51 x 18 x 57 Shipping Weight estimated pounds 400 600 800 NOTE For all other guidelin...

Страница 5: ...low Media Filter Used to remove large suspended solids sediment from the feed water Backwashing the media removes the trapped particles Backwash can be initiated by time or differential pressure Water...

Страница 6: ...nsity index SDI test An SDI of five 5 or less is specified by most mem brane manufacturers and three 3 or less is recommended Iron Manganese Iron should be removed to less than 0 1 ppm Manganese shoul...

Страница 7: ...sure of the prefilter The difference between these two gauges is the prefilter differential pressure F Pump Discharge Pressure Gauge Indicates the pump dis charge pressure G Reject Pressure Gauge Indi...

Страница 8: ...Lync WQ RS SECTION 2 CONTROLS INDICATORS AND COMPONENTS L OMM 005_A 2 23 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 8 of 34 2 2 Controller Drawing Figure 2 2 Controller...

Страница 9: ...Lync WQ RS SECTION 2 CONTROLS INDICATORS AND COMPONENTS L OMM 005_A 2 23 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 9 of 34 Figure 2 3 Controller Continued RO PUMP...

Страница 10: ...be located within 10 feet of the system 2 Temporarily connect the outlet of the product water flow meter to drain Figure 2 1 item B The product water line should never be restricted Membrane and or s...

Страница 11: ...t installed in Section 3 3 step 1 above to apply electrical power to the RO system 11 Press the On Off button on the controller When the pump starts press and hold the On Off button to turn off the pu...

Страница 12: ...this manual for more installation and operation information It is very important to vent the mechanical seal during startup Failure to vent the seal may result in premature seal failure Figure 3 1 Nee...

Страница 13: ...pt Controller Power 24 VAC 60 50Hz Permeate Conductivity 0 3000 PPM 0 6000 s standard sensor CP 1 K 75 Feed Conductivity opt 0 3000 PPM 0 6000 s standard sensor CP 1 K 75 Output Ratings Feed Solenoid...

Страница 14: ...am 5 pm EST 14 of 34 fgdafdfg bd Alternate Wiring Single Tank Level Switch Divert Valve Alarm contacts can be powered or dry contact selectable with switch S1 Close on Fault iControls TB 24V3 Schemat...

Страница 15: ...5654 Mon Fri 8 am 5 pm EST 15 of 34 Figure 3 3 Controller Overview CPU Board Terminal Board Conductivity Probe Connections Programing Transformer Keypad System On Off Up Arrow Down Arrow Manual Run M...

Страница 16: ...Lync WQ RS SECTION 3 OPERATION L OMM 005_A 2 23 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 16 of 34 Pictorial Schematic of a Typical ROC 4 System Figure 3 4 Wiring Diagram...

Страница 17: ...ontroller Detail CPU 4 Shield White Black Shield White Black Main interface port Connects via ribbon cable to Terminal Board Bootload Switch Used for field updates of CPU 4 firmware Programming Port S...

Страница 18: ...Lync WQ RS SECTION 3 OPERATION L OMM 005_A 2 23 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 18 of 34 Figure 3 6 Controller Detail Terminal Board TB 3 For schematic see Figure 2 2 TB24V3...

Страница 19: ...ty Probe in the Run of a Tee or equivalent location Orient the probe so that air cannot become trapped in the area near the probe Figure 3 7 Conductivity Probe Installation Figure 3 8 Input Wiring Con...

Страница 20: ...the Feed Conductivity cell if your system will utilize both feed and permeate conductivity measurement 6 Provide power to the RO system 7 Press the System On Off switch to turn the system ON 8 Select...

Страница 21: ...ump start delay Seconds 10 10 10 10 Inlet Solenoid stop delay Seconds 5 5 1 1 Pump start retry interval restart delay after LP fault Seconds 60 60 60 60 Low pressure fault shutdown of faults Faults 5...

Страница 22: ...Lync WQ RS SECTION 3 OPERATION L OMM 005_A 2 23 2022 Technical Support 800 433 5654 Mon Fri 8 am 5 pm EST 22 of 34 Figure 3 10 Controller Programming Menu Navigation...

Страница 23: ...pressure fault shutdown of faults Faults 5 Low pressure fault shutdown time period to count faults Minutes 10 Low pressure fault shutdown reset after shutdown 0 value no restart Minutes 60 These thre...

Страница 24: ...t Line 3 Line 4 Check Pretreat Sys Permeate Conductivity Fault Permeate conductivity is higher than the alarm set point Line 1 Service Fault Line 2 Permeate TDS xxx ppm or Permeate Cond xxx uS Line 3...

Страница 25: ...PUMP DISCHARGE PRESSURE REJECT PRESSURE FEED TDS PPM PRODUCT TDS PPM FEED WATER TEMP FEED WATER HARDNESS FEED WATER CHLORINE LEVEL PRE FILTER INLET PRESSURE PRE FILTER OUTLET PRESSURE REMARKS Note Cha...

Страница 26: ...SI of reject Calculate maximum solubility for CaSO4 BaSO4 SiO2 in reject analysis Increase acid addition and scale inhibitor for CaSO3 and CaSO4 Reduce recovery Clean with an acid formulation for CaCO...

Страница 27: ...tructive element test Improved pretreatment Check all filters for media leakage Increased Normal to increased Decreased At random O ring leaks End or side seal glue leaks Probe test Vacuum test Colloi...

Страница 28: ...voltage is maintained Check connection Open circuit Fuses blown check overload relay stator and push buttons Motor runs and then dies down Power failure Check for loose connections to line to fuses an...

Страница 29: ...ise Fan rubbing air shield Remove interference Fan striking insulation Clear fan Loose on bedplate Tighten holding bolts Noisy operation Airgap not uniform Check and correct bracket fits or bearing Ro...

Страница 30: ...ssure too low Feed pressure must be at least 20psi Insufficiently flushed post filter cartridge Flush post filter with pure water Brine seal on membrane leaks Determine if seal or O ring is bad Replac...

Страница 31: ...l 4 x 40 FRP bottom 68107309 Flow Meter 1 10 gpm product 7300464 Flow Meter 1 10 gpm reject 7300468 Motor Starter Contactor 16 amps 24 volt coil 7300924 Overload Relay 3 2 16 amps 7300925 Pump and Mot...

Страница 32: ...e out of the vessel in the direction of the feed flow See flow arrows on the right side of Figure 2 1 5 Record the serial numbers of the new membranes 6 Lightly lubricate the brine seals on the new me...

Страница 33: ...tems with reject recycle and a feed water Silt Density Index of 3 to less than 5 MODEL NUMBER WQ RS 005 R WQ RS 010 R WQ RS 015 R Product 2 3 4 3 6 3 Reject 2 3 1 4 2 1 Reject Recycle 4 3 3 9 2 3 Temp...

Страница 34: ...with your Lync system solution Please have your product model number serial number and all relevant information pertaining to your problem ready when calling 1 800 433 5654 Select Option 3 Mon Fri 8...

Отзывы: