23
22
BAS Menu
Modbus Specific Settings
BACnet
®
Analog Parameters
BACnet Standardized Device Profile (ANNEX L)
BACnet Application Specific Controller (B-ASC)
Supported BIBBs (Annex K)
Name
DS-RP-B
Data Sharing-ReadProperty-B
DS-RPM-B
Data Sharing-ReadPropertyMultiple-B
DS-WP-B
Data Sharing-WriteProperty-B
DM-DDB-B
Device Management-Dynamic Device Binding-B
DM-DOB-B
Device Management-Dynamic Object Binding-B
DM-DCC-B
Device Management-Device Communication Control-B
Note: Device communication control password is “PVI1017”.
Segmentation Capability
Supported
Able to transmit segmented messages
No
Able to receive segmented messages
No
Standard Object Types Supported
Creatable
Deletable
Analog Input
No
No
Analog Value
No
No
Binary Output
No
No
Device Address Binding
Supported
Static Device Address Binding
No
Network Security Options
Non-Secure Device
Character Set
Supported
ANSI X3.4
Yes
DigiTemp
®
Jr. BAS Integration Manual
DigiTemp
®
Jr. BAS Integration Manual
Data Link Layer Options
Supported
MS/TP master (Clause 9)
Yes
BACnet IP (Annex J)
No
Objective
Identifier
Objective
Type
Objective Name
Present
Value
Status
Flags
Description
Range/
Value
Event State
Reliability
Out of
Service
Units
0
analog-Input
Mixed Outlet
Temperature
FFF(F/T)
Mixed Outlet
Temperature
0 - 266
Normal
0, 1, 4, 5
FALSE
°F (64)
1
analog-Input
Valve Position
FFF(F/T)
Analog signal pro-
vided to actuator
0 - 10
Normal
0
FALSE
Volts (5)
2
analog-Input
Mixed Outlet High
FFF(F/T)
Highest recorded
mixed outlet
temperature
0 - 266
Normal
0
FALSE
°F (64)
3
analog-Input
Mixed Outlet Low
FFF(F/T)
Lowest recorded
mixed outlet
temperature
0 - 266
Normal
0
FALSE
°F (64)
4
analog-Input
High Temperature
Alert Differential
FFF(F/T)
High Temperature
Alert Differential
10 - 30
Normal
0
FALSE
°F (64)
5
analog-Input
Low Temperature
Alert Differential
FFF(F/T)
Low Temperature
Alert Differential
10 - 30
Normal
0
FALSE
°F (64)
6
analog-Input
High Temperature
Alert Count
FFF(F/T)
Number of High
Temperature Alerts
0 - 65535 Normal
0
FALSE
Number (95)
7
analog-Input
Low Temperature
Alert Count
FFF(F/T)
Number of Low
Temperature Alerts
0 - 65535 Normal
0
FALSE
Number (95)
8
analog-Input
Error Code
FFF(F/T)
Numerical error
code (see error
code table)
1 to 4
Normal
0
FALSE
Number (95)
Others
analog-Input
ERROR
ERROR
ERROR
Communication
error
ERROR
ERROR
ERROR
Analog Valve Objects
Objective
Identifier
Objective
Type
Objective Name
Present
Value
Status
Flags
Description
Range/
Value
Even State
Out of
Service
Units
0
analog-value
Mixed Outlet
Setpoint
FFF(F/T)
Target Tem-
perature
70 - 180
Normal
true to
false
°F (64)
Other
analog-value ERROR
ERROR
ERROR
Communication
error
ERROR
ERROR
ERROR