background image

3

Servicing the First and Second Check Valves

 

Seat

Seat 

O-ring

Disc 

Assembly

Spring

Retainer

Caps/ 

Seat

Cover

Cover O-ring

Retainer

Body

First Check

Second Check

No special tools are required to service the assembly.
1. Remove cover bolts and cover.
2.  Remove the retainer from the body bore. The check valve 

modules can now be removed from the valve by hand or with 

a screwdriver.

3. The check seats are attached to the cage with a bayonet type 

locking arrangement. Holding the cage in one hand, push the 

seat inward and rotate counterclockwise against the cage.  

The seat, spring cage, spring, and disc assembly are now 

individual components.

4. Clean and reassemble the disc assembly. Or depending on 

its condition, discard or replace with a new assembly from the 

repair kit. O-rings should be cleaned or replaced as necessary. 

For more information, refer to repair parts price list PL-RP-BPD.

5. Reassemble the check valve modules. Check modules are 

installed in the valve body with the seats facing the valve inlet. 

The modules must be securely in place before the retainer can 

be replaced.

Check Assemblies

Troubleshooting

SYMPTOM

CAUSE

SOLUTION

 Check valve fails to hold  

1.0 PSID minimum

Debris on check disc sealing surface

Disassemble and clean

Leaking gate valve

Disassemble and clean or repair

Damaged seat disc or seat O-ring

Disassemble and replace

Damaged guide holding check open

Disassemble and clean or replace

Weak or broken spring

Disassemble and replace spring

  Chatter during flow conditions

Worn, damaged or defective guide

Disassemble and repair or replace guide

  Low flows passing through 

mainline valve

Mainline check fouled

Disassemble and clean

Meter strainer plugged

Disassemble and clean

Damaged mainline seat disc or seat

Disassemble and replace

Broken mainline spring

Disassemble and replace

Содержание LF007 IOT Series

Страница 1: ...or plumbing codes the local codes should be followed This product must be installed by a licensed contractor in accordance with local codes and ordinances WARNING Need for Periodic Inspection Mainten...

Страница 2: ...ons Outside Building Above Ground In an area where freezing conditions do not occur Series LF007 can be installed outside of a building See Figure 2 The most satisfactory installation is above ground...

Страница 3: ...as necessary For more information refer to repair parts price list PL RP BPD 5 Reassemble the check valve modules Check modules are installed in the valve body with the seats facing the valve inlet T...

Страница 4: ...irst paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty and the Company shall not be responsible for any incidental special or consequential damages inclu...

Страница 5: ...e plomberie locaux les codes locaux pr valent Ce produit doit tre install par un entrepreneur autoris et respecter les codes et les ordonnances locaux AVERTISSEMENT Besoin d une inspection d une maint...

Страница 6: ...a pas de conditions de gel la s rie LF007 peut tre install e l ext rieur d un b timent Voir la figure 2 L installation la plus satisfaisante est au dessus du sol et doit tre r alis e de cette mani re...

Страница 7: ...ur plus d informations reportez vous la liste de prix des pi ces de r paration PL RP BPD 5 Remonter les modules de clapet antiretour Les modules de clapet sont install s dans le corps de vanne les si...

Страница 8: ...pour transmettre les mesures de pression de l ensemble de la vanne un syst me de gestion du b timent consiste en un module d interface avec trois 3 c bles de capteur un c ble de donn es et un adaptat...

Страница 9: ..._________________________________________________________________________________________________________ ______________________________________________________________________________________________...

Страница 10: ...roduit ne fonctionne pas correctement autres co ts aff rents aux frais de main d uvre de retards de vandalisme de n gligence d engorgement caus s par des corps trangers de dommages caus s par des cond...

Страница 11: ...s reglamentos locales de construcci n o plomer a se deben seguir los reglamentos locales Este producto debe ser instalado por un contratista autorizado de acuerdo con los reglamentos y ordenanzas loca...

Страница 12: ...arse en el exterior de un edificio Consulte la figura 2 La instalaci n m s satisfactoria se realiza sobre el suelo y debe instalarse de esta manera siempre que sea posible En un rea donde se pueden pr...

Страница 13: ...aci n consulte la lista de precios de las piezas de reparaci n PL RP BPD 5 Vuelva a montar los m dulos de la v lvula de retenci n Compruebe que los m dulos est n instalados en el cuerpo de la v lvula...

Страница 14: ...para transmitir mediciones de presi n del conjunto de v lvula a un sistema de gesti n de edificios consta de un m dulo de interfaz con tres 3 cables de sensor cable de datos y adaptador de alimentaci...

Страница 15: ...________________________________________________________________________________________________________ _______________________________________________________________________________________________...

Страница 16: ...funciona correctamente otros costos resultantes de cargos laborales retrasos vandalismo negligencia contaminaci n causada por materiales extra os da os por condiciones adversas del agua productos qu...

Отзывы: