manualshive.com logo in svg
background image

Standard Components

Operation

The Electronic ACV is designed to be electrically positioned to 
control flow, pressure, level or temperature for water applications. 
It is a throttling valve controlled by two 2-way solenoids installed 
in the pilot control system, one connecting the valve cover cham-
ber with upstream pressure and the other connecting the main 
valve cover chamber downstream. By alternately energizing the 
solenoids, line pressure is admitted to or relieved from the cover 
chamber of the main valve, allowing the valve to be "positioned" 
to maintain a desired value. 

The valve is normally interfaced with SCADA systems or a 
Programmable Logic Controller that compares a Process Variable 
(PV) to a desired setpoint, and energizes the solenoid pilots to 
throttle the valve open or closed until the PV reaches the desired 
setpoint. 

1

X

X

X

Y/FC

4

2

SB

3

SB

P/L/A

5

X

CLOSES VALVE

OPENS VALVE

FLOW

1.  Prior to installation, flush line to remove debris.

2.  Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures. A Position 

Indicator can be installed to provide visual indication of valve position and operation without disassembly.

3.  Install isolation valves upstream and downstream of the main valve.

4.  Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page. Avoid installing 

valves 6" and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are designed for horizon-
tal in-line installation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and guide wear may 
occur if valve is not installed according to factory recommendations. Consult factory for detailed engineering review prior to order-
ing if valve is to be installed other than horizontally in-line.

5.  If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit 

from damage. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean and 
replaced exactly as removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.

6.  Connect solenoid wiring leads to desired switching device, using safe, standard electrical practices.

7.  After installation, vent entrapped air from valve cover and pilot system by following instructions on Technical Bulletin.

Start-up of an automatic control valve requires that proper procedures be followed. Time must be allowed for the valve to react to 
adjustments and the system to stabilize. The objective is to bring the valve into service in a controlled manner to protect the system 
from damaging over-pressure.

Rate of valve operation is controlled by separate adjustable Opening and Closing Speed Controls that control the rate fluid and pressure 
are admitted to or relieved from the main valve cover chamber. 

The valve is constructed with two "normally closed" solenoids allowing the valve to "hold last position" upon power failure. The valve 
may also be configured to open fully or close drip tight upon power failure if desired. 

Specify valve to "hold last position", "open fully" or "close drip tight" upon power failure PRIOR to ordering.

1 – Main Valve (905GD - Single Chamber)
2 – 2-Way Solenoid (closing)
3 – 2-Way Solenoid (opening)
4 – Adjustable Closing Speed
5 – Adjustable Opening Speed
SB – Solenoid Bypass
X – Isolation Cocks

Installation

933GD (Globe) Electronic Control Valve (for Electric Valve Positioning)

2          IOM-A-ACV-933_633   2115 

EDP# 1917088 

© 2021 Watts

Содержание AMES 933GD

Страница 1: ...Setting the Solenoid Control Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to th...

Страница 2: ...talled according to factory recommendations Consult factory for detailed engineering review prior to order ing if valve is to be installed other than horizontally in line 5 If valve is equipped with a...

Страница 3: ...valve bleed air by loosen ing a fitting on the valve or a plug at the highest point of the valve assembly STEP 5 Pressure the line by opening the upstream isolation valve slowly Air is vented through...

Страница 4: ...r of the main valve If the main valve is opening too slowly turn the adjustment screw OUT counterclockwise increasing the rate of opening See Figure 2B If the main valve is opening too quickly turn th...

Страница 5: ...ve specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphr...

Страница 6: ...ck isolation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembly corroded damaged Inspect stem assembly clean replace if necess...

Страница 7: ...Remove cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may requi...

Страница 8: ...e brush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thr...

Страница 9: ...r Nuts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the inte...

Страница 10: ...s Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 13 Seat Disc Buna N Nitrile 14 Spacer...

Страница 11: ...IOM A ACV 933_633 2115 EDP 1917088 2021 Watts 11 NOTES...

Страница 12: ...sts resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no c...

Отзывы: