Issue

Possible Cause

Corrective Action

Notes

Main Valve will not 
open

Closed isolation valves in pilot system.

Check isolation valves, ensure 
open. 

Insufficient supply pressure.

Check upstream pressure.

Depending on water 
source, supply pressure 
may not be controlled by 
valve operator.

Main valve stem assembly corroded/
damaged

Inspect stem assembly, clean/
replace if necessary.

Blockage in pilot system.

Inspect & clean any installed 
pilot system strainers, check 
orifice/speed controls for 
blockages.

Improperly configured opening speed 
control. 

Adjust opening speed control 
to verify functionality, adjust as 
required.

Standard setting for open-
ing speed control is 1 1/2 
- 2 1/2 turns open from full 
closed position. Can be 
adjusted in field. 

Inlet solenoid by-pass valve is open

Close inlet solenoid by-pass 
valve

Main Valve will not 
close

Closed isolation valves in pilot system

Check isolation valves, ensure 
open. 

Diaphragm is damaged

Conduct diaphragm seal test, 
repair and replace if necessary. 

Main valve stem assembly corroded/
damaged.

Inspect stem assembly, clean/
replace if necessary.

Blockage in main valve.

Perform freedom of movement  
test; if valve does not close,  
disassemble and remove  
blockage.

Worn/damaged valve seat. 

Perform  seat sealing check; 
disassemble and inspect/re-
pair seat if required.

Improperly configured closing speed 
control.

Adjust closing speed control 
to verify functionality, adjust as 
required.

Standard setting for 
closing speed control is 
11/2 - 21/2 turns open from 
full closed position. Can 
be adjusted in field.

Outlet solenoid by-pass valve is open

Close outlet solenoid by-pass 
valve

Solenoid will not 
actuate

Low or no voltage

Check voltage at the solenoid 
connection, insuring that it has 
the minimum of 85% of the 
coils rated voltage.

Should be performed by 
licensed electrician

Manual operated is engaged

Turn manual operator counter-
clockwise to disengage

Troubleshooting Guide

 

6          IOM-A-ACV-933_633   2115 

EDP# 1917088 

© 2021 Watts

IOM-A-ACV-933_633   2115 

EDP# 1917088 

© 2021 Watts         7

Содержание AMES 933GD

Страница 1: ...Setting the Solenoid Control Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to th...

Страница 2: ...talled according to factory recommendations Consult factory for detailed engineering review prior to order ing if valve is to be installed other than horizontally in line 5 If valve is equipped with a...

Страница 3: ...valve bleed air by loosen ing a fitting on the valve or a plug at the highest point of the valve assembly STEP 5 Pressure the line by opening the upstream isolation valve slowly Air is vented through...

Страница 4: ...r of the main valve If the main valve is opening too slowly turn the adjustment screw OUT counterclockwise increasing the rate of opening See Figure 2B If the main valve is opening too quickly turn th...

Страница 5: ...ve specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphr...

Страница 6: ...ck isolation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembly corroded damaged Inspect stem assembly clean replace if necess...

Страница 7: ...Remove cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may requi...

Страница 8: ...e brush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thr...

Страница 9: ...r Nuts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the inte...

Страница 10: ...s Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 13 Seat Disc Buna N Nitrile 14 Spacer...

Страница 11: ...IOM A ACV 933_633 2115 EDP 1917088 2021 Watts 11 NOTES...

Страница 12: ...sts resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no c...

Отзывы: