AM Series Boiler & Water Heater User Manual
CHAPTER 8
– UNIT START-UP
OMM-0100_E
•
GF-146
•
11/15/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 99 of 170
Gas Supply Pressure Test
- Continued
8.
Generate a heat demand as follows, for appropriate type (boiler or water heater):
•
BOILER or WATER HEATER:
by pressing button
to its maximum setting.
•
INDIRECT WATER HEATER:
by pressing button
to its maximum setting.
9.
Gain access to the installer menu (See Section 9.16) and set parameter 2200 to HIGH. Now
the unit will run for 20 minutes at maximum input.
10.
Check the man
ometer to make sure the gas supply pressure does not drop below 3” W.C.
(7.6 m
bar). If the gas supply pressure is lower than 3” W.C. it means that your inlet gas line
or your gas pressure regulator is not correctly sized.
CAUTION!
DO NOT adjust the screw
“F” (Figure 8-2). This screw is factory-set for the correct gas flow
and outlet pressure. Attempting to alter the gas valve setting could result in damage to the
valve, causing potential severe personal injury, death, or substantial property damage.
11.
After verifying the correct gas pressures:
a) Return to parameter 2200 and set to OFF.
b) Close the manual gas shut-off valve (Figure 7-1).
c) Disconnect the manometer.
d) T
urn the screw in pressure connection “D” in Figure 8-2, clockwise until snug.
e)
Check pressure port “D” (Figure 8-2) for any gas leaks.