AM Series Boiler & Water Heater User Manual
CHAPTER 7: INSTALLATION
– NATURAL GAS
OMM-0100_E
•
GF-146
•
11/15/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 91 of 170
Gas Rating Conversion of Burners 2, 3, and 4
After converting
Burner 1 (Master)
, you must convert
Burner 2
,
Burner 3
(if present), and
Burner 4
(if present). Refer to Figure 7-6 and perform the following steps:
1.
Turn the power OFF to the unit.
Burner 2:
2.
Disconne
ct plug “B” from connector “A”.
3.
Connect plug “B” to connector “C”.
4.
Repeat Step 1 through Step 20 of the
previous instructions “
Gas Rating Conversion of
Master Burner”.
5.
Ensure power is still OFF to the unit.
Burner 3 (
if present):
6.
Disconnect plug “B” from connector “C”.
7.
Connect plug “B” to connector “D”.
8.
Repeat Step 1
through Step 20 of the previous instructions “
Gas Rating Conversion of
Master Burner”.
9.
Ensure power is still OFF to the unit.
Burner 4 (
if present)
:
10.
Disconnect plug “B” from connector “D”.
11.
Connect plug “B” to connector “E”.
12.
Repeat Step 1 through Step
20 of the previous instructions “
Gas Rating Conversion of
Master Burner”.
After converting all burners:
13.
C
onnect plug “B” to plug “A”.
14.
Check the inlet gas pressure of the unit, per Section 8.6.
15.
Attach to the front of the heater the appropriate conversion label, found in the conversion kit
stating the new type of gas adjustment of the heater as follow:
a) Apply the label in Figure 7-7 if the heater has been converted to PROPANE GAS.
b) Apply the label in Figure 7-8 if the heater has been converted to NATURAL GAS.