10.17 Inspecting and Replacing the Burner Thermal Insulation
The thermal insulation in each burner must be inspected every year for any damage, including
cracks, chips, or other abnormalities. If any damage is found, the insulation must be replaced
using the instructions below. The replacement procedure must be repeated on each burner
module in the unit.
Replacing the BURNER Thermal Insulation
1.
Follow Steps 1 through 11 of the instructions in section 6.1.16 in order to remove the fan
and burner assembly from the heat exchanger.
2.
Unscrew the screws holding the electrodes in place (see Figure E).
3.
Remove both the ignition and flame detection electrodes (see Figure F).
Figure E: Removing
Electrode’s Screws Figure F: Removing the Electrodes
4.
Remove the
burner’s thermal insulation (see Figure G).
5.
Replace the O-Ring (see arrow in Figure H) with the new one included in the kit.
Figure G: Remove Thermal Insulation Figure H: Replace the O-
Ring