3.7.2 Innovation 600N Combustion Air Duct Pressure Drop Tables
•
Values for
Straight Run
are equivalent feet per foot or meters per meter
•
Values for
90° Elbow
,
45° Elbow
, and
Ent. Loss
are equivalent feet (equivalent
millimeters)
TABLE 5: Innovation 600N MBTU (176 kW)
Water Heaters
Inlet Duct
& No.
Units
Duct
Section
Type
Outside Air Temperature
-30 °F
-15 °F
0 °F
20 °F
40 °F
60 °F
80 °F
100 °F
120 °F
-34 °C
-26 °C
-18 °C
-7 °C
4 °C
16 °C
27 °C
38 °C
49 °C
6" Duct
Single Unit
Straight Run
0.19
0.2
0.2
0.21
0.21
0.22
0.23
0.24
0.24
90° Elbow
0.82
0.86
0.9
0.96
1.02
1.09
1.16
1.24
1.32
(250)
(262)
(274)
(293)
(311)
(332)
(354)
(378)
(402)
45° Elbow
0.60
0.63
0.67
0.71
0.76
0.81
0.86
0.92
0.98
(183)
(192)
(204)
(216)
(232)
(247)
(262)
(280)
(299)
Ent. Loss
1.27
1.33
1.4
1.49
1.59
1.7
1.81
1.94
2.06
(387)
(405)
(427)
(454)
(485)
(518)
(552)
(591)
(628)
8" Duct
Single Unit
Straight Run
0.05
0.05
0.05
0.05
0.05
0.05
0.06
0.06
0.06
90° Elbow
0.21
0.22
0.23
0.24
0.26
0.28
0.30
0.32
0.34
(64)
(67)
(70)
(73)
(79)
(85)
(91)
(98)
(104)
45° Elbow
0.16
0.16
0.17
0.18
0.2
0.21
0.22
0.24
0.25
(49)
(49)
(52)
(55)
(61)
(64)
(67)
(73)
(76)
Ent. Loss
0.40
0.42
0.44
0.47
0.5
0.54
0.57
0.61
0.65
(122)
(128)
(134)
(143)
(152)
(165)
(174)
(186)
(198)
8" Duct
Two Units
Straight Run
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.22
0.23
90° Elbow
0.83
0.87
0.92
0.98
1.04
1.11
1.19
1.27
1.35
(253)
(265)
(280)
(299)
(317)
(338)
(363)
(387)
(411)
45° Elbow
0.63
0.66
0.69
0.74
0.79
0.84
0.90
0.96
1.02
(192)
(201)
(210)
(226)
(241)
(256)
(274)
(293)
(311)
Ent. Loss
1.61
1.69
1.77
1.89
2.02
2.15
2.30
2.45
2.61
(491)
(515)
(539)
(576)
(616)
(655)
(701)
(747)
(796)
10" Duct
Two Units
Straight Run
0.05
0.05
0.05
0.06
0.06
0.06
0.07
0.07
0.08
90° Elbow
0.30
0.31
0.33
0.35
0.37
0.40
0.42
0.45
0.48
(91)
(94)
(101)
(107)
(113)
(122)
(128)
(137)
(146)
45° Elbow
0.23
0.24
0.25
0.27
0.28
0.3
0.32
0.35
0.37
(70)
(73)
(76)
(82)
(85)
(91)
(98)
(107)
(113)
Ent. Loss
0.66
0.69
0.73
0.77
0.83
0.88
0.94
1.00
1.07
(201)
(210)
(223)
(235)
(253)
(268)
(287)
(305)
(326)
TABLE 5: Innovation 600N MBTU (176 kW)
Water Heaters
–
Continued
Outside Air Temperature
-30 °F
-15 °F
0 °F
20 °F
40 °F
60 °F
80 °F
100 °F