6 . 2 2
■
P a r a m e t e r s
Wa t l o w P o w e r S e r i e s
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Address
Parameters to Appear
read/write
*
NOTE: The display prompts are set to two decimal places because of the resolution of the display.
The comms registers are set and stored with three decimal places of resolution.
Active if in factory mode.
Active if retransmit option is
installed.
5700 r/w
[idle]
cali-
bration
inactive (0)
[`Err]
invalid calibra-
tion (-1)
[idle]
calibration
inactive (0)
[`req]
enables cali-
bration request (1)
[CALr]
Cal Retransmit
Request
Request a retransmit
calibration.
Active if in factory mode.
Active if retransmit option is
installed.
5721 r/w
[(000]
(9000)
[UOL_]
to
[(999]
(Retransmit Cal Volts
Low to 9999)
[Uol–]
Retransmit Cal
Volts High
Set the high voltage
value for retransmit
cal.
Active if in factory mode.
Active if retransmit option is
installed.
5720 r/w
[!000]
(1000)
[```0]
to
[UOL–]
(0 to Retransmit Cal
Volts High)
[Uol_]
Retransmit Cal
Volts Low
Set the low voltage
value for retransmit
cal.
Active if in factory mode.
Active if retransmit option is
installed.
5711 r/w
[1^00]
(16000)
[nnA_]
to
[2)00]
(Retransmit Cal mA
Low to 20000)*
[nna–]
Retransmit Cal
mA High
Set the high current
value for retransmit
cal.
Active if in factory mode.
Active if retransmit option is
installed.
5710 r/w
[$000]
(4000)
[)000]
to
[nna–]
[or
[(999]
whichever is
smaller]
(0 to Retransmit Cal
mA High [or 9999])
[nna_]
Retransmit Cal
mA Low
Selects the low
current value for
retransmit cal.
[C|rtr]
Calibrate Retransmit Menu
[Fcty]
Factory Page
This menu is used to calibrate the retransmit output. This menu is available if Retransmit is
installed.
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.