Active if retransmit and heater
diagnostics options are installed.
Active if
[`Cfg]
is set to
[`nna]
.
883 r/w
[2)00]
(2000)
[rt|C_]
to
[2)00]
(Retransmit Output
Low Current to 2000)
[rt|C–]
Retransmit Out-
put High Current
(mA)
Select output
current that will
correspond to
[Cur–]
or
[HUA–]
.
Active if retransmit and heater
diagnostics options are installed.
Active if
[`Cfg]
is set to
[`nna]
.
882 r/w
[```0]
(0)
[`)00]
to
[rt|C–]
(0 to Retransmit Out-
put High Current)
[rt|C_]
Retransmit Out-
put Low Current
(mA)
Select output
current that will
correspond to
[Cur_]
or
[HUA_]
.
Active if retransmit and heater
diagnostics options are installed.
Active if
[retr] ® [type]
is set
to
[`HUa]
.
879 r/w
[9999]
(9999)
[HUA_]
to
[9999]
(Minimum kVA Re-
transmit to 9999)
HUA–]
Maximum kVA
Retransmit
Select maximum
load power to be
retransmitted.
Active if retransmit and heater
diagnostics options are installed.
Active if
[retr] ® [type]
is set
to
[`HUa]
.
878 r/w
[```0]
(0)
[```0]
to
[HUA–]
(0 to Maximum kVA
Retransmit)
[HUA_]
Minimum kVA
Retransmit
Select minimum
load power to be
retransmitted.
Active if retransmit and heater
diagnostics options are installed.
Active if
[retr] ® [type]
is set
to
[`Cur]
.
877 r/w
load current
[Cur_]
to load current
(Minimum Amps Re-
transmit to load cur-
rent)
[Cur–]
Maximum Amps
Retransmit
Select maximum
load current to be
retransmitted.
Active if retransmit and heater
diagnostics options are installed.
Active if
[retr] ® [type]
is set
to
[`Cur]
.
876 r/w
[``00]
(0)
[```0]
to
[Cur–]
(0 to Maximum Amps
Retransmit)
[Cur_]
Minimum Amps
Retransmit
Select minimum
load current to be
retransmitted.
Active if retransmit and heater
diagnostics options are installed.
Active if controller is multi zone.
Active if
[retr] ® [type]
is set
to
[`CUr]
or
[`HUa]
.
873 r/w
[```1]
zone1
(1)
[```1]
zone1 (1)
[```2]
zone2 (2)
[```3]
zone3 (3)
[2one]
Retransmit Zone
Select
Select the zone with
information to be
retransmitted.
Active if retransmit and heater
diagnostics options are installed.
Active if controller is three phase.
Active if
[retr] ® [type]
is set
to
[`CUr]
or
[`HUa]
.
872 r/w
[```1]
phase
1 (1)
[```1]
phase 1 (1)
[```2]
phase 2 (2)
[```3]
phase 3 (3)
[PhaS]
Retransmit Phase
Select
Select the phase
with information to
be retransmitted.
P a r a m e t e r s , C h a p t e r 6
Wa t l o w P o w e r S e r i e s
■
6 . 1 3
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Control
Methods and Features.
Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Register
Parameters to Appear
read/write