Display
Parameter
Range
Default
Modbus
Conditions for
(Modbus Value)
Address
Parameters to Appear
read/write
6 . 6
■
Wa t l o w P o w e r S e r i e s
P a r a m e t e r s , C h a p t e r 6
Active: Always.
80 r/w
[``ON]]
on
(0)
[``ON]
on (0)
[`Off]
off (1)
[``UC]
Line Voltage Com-
pensation
Automatically adjusts
output duty cycle to
compensate for line
voltage fluctuations.
Occurs for requested
power from 5% to
95% and only applies
to variable time base
or phase angle con-
trol methods.
[Ctr1] [Ctr2] [Ctr3]
Setup Control Zone 1, 2, and 3 Menus
[`Set] [`Set]
[`Set]
Setup Page
This menu is used to set up the control for the chosen zone.
Zone 1 is used if Input/Output Configuration is single phase, single zone, or three phase.
Zone 1 and 2 are used if Input/Output Configuration is single phase, two zones.
All zones are used if Input/Output Configuration is single phase, three zones.
Active: Always.
[`dig]
is not available if
[Set`]
® [algo]
in the Setup Page is
set to
[cont]
.
5101 r/w [1]
5201 r/w [2]
5301 r/w [3]
[`nna]
cur-
rent (1)
[`OFF]
off (0)
[`nna]
current (1)
[Uolt]
voltage (2)
[`dig]
keyboard or
comms (3)
[``In]
Input Signal
Method Select
(dig, mA, Volt)
Select the input
signal method for
chosen zone.
Active if input signal method is
set to
[`dIG]
.
5103 r/w [1]
5203 r/w [2]
5303 r/w [3]
[``)0]
(0)
[``)0]
0 percent to
[10)0]
100 percent
(0 to 1000)
[dFlt]
Default Numeric
Input Signal (%)
Selects the power-on
level for chosen zone.
Active if
[``In]
is set to
[`nna]
current.
5011 r/w [1]
5021 r/w [2]
5031 r/w [3]
[`)00]
(0)
[`)00]
to
[nna–]
[0 to mA high -5mA]
[nna_]
Analog Input Low
Current (mA)
Sets current value
which will corre-
spond to 0% power if
input is current type.
Active if
[``In]
is set to
[`nna]
current.
5012 r/w [1]
5022 r/w [2]
5032 r/w [3]
[2)00]
(2000)
[nna_]
[+ 5mA] to
[9(99]
[low mA + 5mA to mA
9999]
[nna–]
Analog Input High
Current (mA)
Sets current value
which will corre-
spond to 100%
power if input is
current type.
Active if
[``In]
is set to
[Uolt]
voltage.
5013 r/w [1]
5023 r/w [2]
5033 r/w [3]
[`)00]
(0)
[`)00]
to
[Uol–]
[- 2.5V]
[0 to V high -2.5V]
[Uol_]
Analog Input Low
Voltage (Volts)
Sets voltage value
which will corre-
spond to 0% power if
input is voltage type.
Содержание PC1X-F20
Страница 4: ...ii Watlow Power Series Table of Contents...
Страница 72: ......