Additional generator (Boiler connection)
3700
S
Release under outdoor temperature
--, -50... 50 °C
0,5 °C
2 °C
3705
S
Overrun time
0... 120 min
1 min
20 min
3720
S
Switching integral (for boiler relief)
0... 500 °Cmin
1 °Cmin
100 °Cmin
3723
S
Locking time
1... 120 min
1 min
30 min
Domestic hot water (DHW) (Only with the DHW kit option)
5020
S
Flow setpoint boost
0... 30 °C
1 °C
5 °C
5024
S
Switching diff
0... 20 °C
1 °C
7 °C
5030
S
Charging time limitation
10... 600 min
10 min
90 min
5060
S
Electrical resistance regime
Substitute, Summer, Always,
Cooling mode
Substitute
5061
S
Electrical resistance release
24h / day, Release of DHW,
Programme 4 / DHW
Release of
DHW
Installation configuration
5700
I
Pre-setting
1,2,3,... 12
1
1
This control enables you to choose one of the 8 pre-selected installation configurations. The hydraulic layouts for the
various configurations are detailed in the section : "Installation Configurations".
- Pre-setting 1 : 1 heating circuit
- Pre-setting 2 : 1 heating circuit and DHW tank.
- Pre-setting 3 : 2 heating circuits.
- Pre-setting 4 : 2 heating circuits and DHW tank.
- Pre-setting 5 : Boiler connection and 1 heating circuit.
- Pre-setting 6 : Boiler connection and 2 heating circuits
- Pre-setting 7 : Boiler connection, 1 heating circuit and DHW tank.
- Pre-setting 8 : Boiler connection, 2 heating circuits and DHW tank.
- Pre-setting 9 to 12 : Do not use for heat pump single service. Reserved only for heat pump 2 services.
5711
S
Cooling circuit 1
Off, System with 4 tubes,
System with 2 tubes
Off
5870
S
Combi storage tank
No, Yes
No
5987
S
Cont type input EX4
Normally-closed contact (NC)
Normally-opened contact (NO)
NO
5989
S
Cont type input EX5
Normally-closed contact (NC)
Normally-opened contact (NO)
NC
6046
I
Function input H2
1 - Operating mode change HCs + DHW
2 - Operating mode change HCs
3 - Operating mode change HC1
4 - Operating mode change HC2
6 - Error/alarm message
9 - Dew point monitoring
16 - Swimming pool release
1 16
1
9
6047
I
Contact type H2
NC - Normally-closed,
NO - Normally-opened
NO
6048
S
Function value contact H2
0... 130 °C
1 °C
45 °C
6100
S
Readjustm outside sensor
-3... 3 °C
0,1 °C
0 °C
6120
S
Frost protection plant
On, Off
On
6205
S
Reset to default parameters
No, Yes
No
6220
S
Software version (RVS)
0 99
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Installation and operating manual "1364 - EN"
- 41 -
Split system (3-phase)