46
I
Operation HCP (domestic hot water pump command, output QX2)
Commonly with
HC1
Commonly with HC1 or Independent (if independent, see timer program 3 / HCP)
70
S
Software version (Display)
Heating time programme, circuit 1
500
U
Pre-selection (Day / Week)
Mon-Sun Mon-Fri Sat-Sun
Monday Tuesday…
Mon-Sun
501
U
1
st
phase On (start)
00:00... --:--
10 min
6:00
502
U
1
st
phase Off (end)
00:00... --:--
10 min
22:00
503
U
2
nd
phase On (start)
00:00... --:--
10 min
--:--
504
U
2
nd
phase Off (end)
00:00... --:--
10 min
--:--
505
U
3
rd
phase On (start)
00:00... --:--
10 min
--:--
506
U
3
rd
phase Off (end)
00:00... --:--
10 min
--:--
516
U
Default values, Circuit 1
No, Yes
No
Yes + OK : The Default values memorised in the regulator replace and cancel the customised heating programmes.
Your customised settings are therefore lost.
Heating time programme, circuit 2
Only with the 2nd circuit kit option
520
U
Pre-selection (Day / Week)
Mon-Sun Mon-Fri Sat-Sun
Monday Tuesday…
Mon-Sun
521
U
1
st
phase On (start)
00:00... --:--
10 min
6:00
522
U
1
st
phase Off (end)
00:00... --:--
10 min
22:00
523
U
2
nd
phase On (start)
00:00... --:--
10 min
--:--
524
U
2
nd
phase Off (end)
00:00... --:--
10 min
--:--
525
U
3
rd
phase On (start)
00:00... --:--
10 min
--:--
526
U
3
rd
phase Off (end)
00:00... --:--
10 min
--:--
536
U
Default values, Circuit 2
No, Yes
No
Yes + OK : The Default values memorised in the regulator replace and cancel the customised heating programmes.
Your customised settings are therefore lost.
Programme 3/ HCP
Domestic hot water pump program, lines 540 to 556.
Time programme 4 / DHW
If the installation is fitted with a DHW tank. (Only with the DHW kit option).
560
U
Pre-selection (Day / Week)
Mon-Sun Mon-Fri Sat-Sun
Monday Tuesday…
Mon-Sun
561
U
1
st
phase On (start)
00:00... --:--
10 min
00:00
562
U
1
st
phase Off (end)
00:00... --:--
10 min
05:00
563
U
2
nd
phase On (start)
00:00... --:--
10 min
--:--
564
U
2
nd
phase Off (end)
00:00... --:--
10 min
--:--
565
U
3
rd
phase On (start)
00:00... --:--
10 min
--:--
566
U
3
rd
phase Off (end)
00:00... --:--
10 min
--:--
576
U
Default values
No, Yes
No
Yes + OK : The Default values memorised in the regulator replace and cancel the customised heating programmes.
Your customised settings are therefore lost.
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Installation and operating manual "1364 - EN"
- 35 -
Split system (3-phase)