Line
Function
Setting range
or display
Setting
increment
Basic
setting
LPB system
6600
S
Not used
Error
6711
U
Reset HP
No, Yes
No
6800
S
History 1
Time, Date, Error code
6802
S
History 2
Time, Date, Error code
6804
S
History 3
Time, Date, Error code
6806
S
History 4
Time, Date, Error code
6808
S
History 5
Time, Date, Error code
6810
S
History 6
Time, Date, Error code
6812
S
History 7
Time, Date, Error code
6814
S
History 8
Time, Date, Error code
6816
S
History 9
Time, Date, Error code
6818
S
History 10
Time, Date, Error code
Maintenance / special regime
7070
S
HP interval
--, 1... 240
1 month
--
7071
S
HP time since maint
Reset ? (no, yes)
0 240
1 month
0
7073
S
Cur starts compr1/hrs run (since the 6 last weeks)
Reset ? (no, yes)
0 12
0
7141
U
Emergency operation
Off, On
Off
Off: Heat pump functions normally (with boosters if necessary).
On: Heat pump uses the electric boost system or the boiler connection.
Use the “On” position only in Assist mode or Test mode: may result in high power bills.
7142
S
Emergency operating function type
Manual, Automatic
Manual
Manual: Emergency mode is not active when a fault occurs (Emergency mode = OFF).
Automatic: Emergency mode is active when a fault occurs (Emergency mode = ON).
In "Automatic" position, the energy cost can be onerous if the error is not detected and eliminated.
7150
I
Simulation outside temp
-50... 50 °C
0,5
--
Inputs / outputs test
7700
I
Relay test
0
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check that
the relays are working and that the cabling is correct. Check that each appliance in the installation is operating correctly.
(0) No test, (1) Everything is on STOP, (2) Relay output QX1 : heat pump CC1 (Main regulation board), (3) Relay output QX2 :
Electrical back-up (1st stage) or Boiler connection distribution valve, (4) Relay output QX3 : Electrical back-up (2nd stage) or
Boiler connection contact, (5) Relay output QX4 : DHW distribution valve, (6) Relay output QX5 : DHW Electrical back-up,
(7) Relay output QX6 , (8) Relay output QX31 : Heat circ mix valve open Y1 (or Control pilot-wire), (9) Relay output QX32 :
Heat circ mix valve close Y2, (10) Relay output QX33 : heat pump CC2, (11) Relay output QX34, (12) Relay output QX35 : Swimming
pool distribution valve, (13) Relay output QX21 module 1, (14) Relay output QX22 module 1, (15) Relay output QX23 module 1,
(16) Relay output QX21 module 2, (17) Relay output QX22 module 2, (18) Relay output QX23 module 2, (19) Not used,
(20) Not used, (21) Not used.
The display shows the “Key” symbol. Pressing the Info button displays "Error 368".
Warning: The component being tested is receiving electrical power throughout the test.
7710
I
Output UX1 test
0... 100%
1
--
7712
I
PWM signal UX1
0... 100%
1
0
7716
I
Output UX2 test
0... 100%
1
--
7719
I
PWM signal UX2
0... 100%
1
0
7722
I
Cooling mode D2
Off, On
Off
7723
I
Heat pump D3
Off, On
Off
Installation and operating manual "1532 - EN"
- 43 -
Air to Water Heat Pump