Heating, circuit 2
Only with the 2nd circuit kit option (If the installation consists of 2 heating circuits).
1010
U
Comfort setpoint
Reduced setpoint…
Comfort setpoint maximum
0,5 °C
20 °C
1012
U
Reduced setpoint
Frost protection setpoint…
Comfort setpoint
0,5 °C
19 °C
1014
U
Frost protection setpoint
4 °C… Reduced setpoint
0,5 °C
8 °C
1016
S
Comfort setpoint maximum
Comfort temp... 35 °C
1 °C
28 °C
1020
I
Heating curve slope (
0,1... 4
0,02
0,5
1021
I
Heating curve displacement (
)
-4,5... 4,5 °C
0,5 °C
0 °C
1026
I
Heating curve adaption
Off, On
Off
Warning !
Not to modify, let on "Off".
1030
I
Summer / Winter heating limits
8 30 °C
0,5 °C
18 °C
When the average of the outside temperatures over the past 24 hours reaches 18°C, the regulator switches off the heating
(as an economy measure). During summer mode, the display shows "Eco". This function is only active in automatic mode.
1032
S
24-hour heating limit
-10... 10 °C
1 °C
-2 °C
This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons.
Increasing the value delays the switchover to summer regime.
Decreasing the value advances the switchover to summer regime.
This function is only active in automatic mode.
1040
I
Flow temp setpoint min (for fan convector)
8 70 °C
1 °C
8 °C
1041
I
Flow temp setpoint max
8 70 °C
1 °C
55 °C
Floor heating system = 50 °C / Radiators = 65 °C.
Important Note :
Maximum temperature limitation is not a safety function as required by ground heating.
1050
S
Room influence
1 %... 100 %
1 %
50 %
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1080
S
Quick setback
Off, Down to reduced setpoint,
Down to frost prot setpoint
Down to
reduced
setpoint
1090
S
Optimum start control max
0... 360 min
10 min
180 min
1091
S
Optimum stop control max
0... 360 min
10 min
60 min
1100
S
Reduced setpoint increase start
-30... 10 °C, --°C
1 °C
--
1101
S
Reduced setpoint increase end
-30... 10 °C, --°C
1 °C
-5 °C
1130
S
Mixer valve increase
0 50 °C
1 °C
0 °C
1134
S
Actuator running time
30... 873 s
1 s
240 s
1150
I
)
Off
- Off: Early interruption of the current program, program inactive.
- Functional heating.
- Heating ready for occupation.
- Functional h Curing heating.
- Curing h Functional heating.
- Manually: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
1151
I
Floor curing setpoint manually
(if line 1150 = manual)
0 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying program stops automatically after running for 25 days.
1156
I
Floor curing day current
0 32
1157
I
Floor curing day completed
0 32
0