7
- Electrical Connection -
1. Connect the power supply to the control valve and plug into a 115 volt / 60 Hz receptacle.
Note:
Do not plug into an outlet controlled by a wall switch or pull chain that could inadvertently be
turned off.
-*Pressurizing The System -
2. Slowly rotate handle of the bypass valve to the SERVICE position.
3. Open the nearest faucet to evacuate air from plumbing lines.
4. Check for leaks! If water is observed leaking from bypass, o-rings on valve body may not be seated prop
erly. Exercise bypass valve.
5. After air is evacuated from plumbing lines, turn off faucet.
- Initial Control Valve Operation -
1. Advance control valve to BACKWASH (cycle 1) position and allow water to run to drain for 3 to 4 minutes.
Electronic Connections
P - Power Supply
B - Powered in Backwash Step Only (Cycle #1)
S - Powered in Entire Regeneration Cycle
- Drain Line Connection -
1. The drain line flow control assembly is pre-assembled for your convenience. Should you choose to hard
plumb the drain line, please remove the barb fitting. The flow control housing can be removed by remov
ing the clip and pulling straight out on housing.
Note:
When re-installing the drain line flow control housing, be sure you hear and feel the O-Ring pop into
place before inserting the clip.
2. Install 1/2” I.D. drain line tubing (not included) from hose barb to an open drain. A 4” gap between end of
the drain line and the open drain is required to prevent waste water backflow. Keep the drain line as
short as possible. An overhead drain line can be used if necessary, but should discharge below the con
trol valve. A syphon trap (taped loop) at the outlet of the drain line is advisable to keep the drain line full
and assure correct flow during backwash. Elbows or other fittings must be kept at a bare minimum.
Note:
Where the drain line is elevated above the control valve or exceeds 20 feet in length, 3/4” I.D. drain
line tubing should be used.
P B S
- Air Compressor / Relay Box –
• Locate the air compressor in close proximity to the AP tank assembly.
• Connect the supplied tubing to the compressor and the other end to the AP tank manifold insert.
• Insert the compressor’s electrical plug into the relay box.
• Insert the electrical plug from the relay box to an unswitched 120v / 60Hz grounded outlet.
• Attached by the relay box is a red and white RCA cable which plugs into the “B” and “S” outputs of the
control valve.
Note: As water flow through the filter, the meter will turn and send a signal to the relay box and the
relay box will turn on the air compressor. Make sure air compressor switch is turned on.
Installation