Waterous
200-B Belt-Driven Installation Guide
Rev-
Page 26 of 54
8
Repeat closing the PBTV one full turn until the air pressure is equal to or up to
5% higher than the water pressure.
9
If the air pressure is too high after a full-turn of the PBTV, turn the Air Inlet Trim
Valve clockwise to lower the pressure until the air pressure is equal to or up to
5% higher than the water pressure.
10 Verify the Auto-Sync system settings by varying the fire pump discharge
pressure and monitoring the water and air pressure gauges. The air pressure
should rise and fall with the water pressure, matching it within 5%.
Pressures should match at static pressure only. It is normal for the pressures to
be unmatched when flowing water, air, or solution.
Содержание 200-B
Страница 39: ...Waterous 200 B Belt Driven Installation Guide Rev Page 39 of 54 Figure 33 Basic CAFS System...
Страница 40: ...Waterous 200 B Belt Driven Installation Guide Rev Page 40 of 54 Figure 34 200 B with T Sump...
Страница 41: ...Waterous 200 B Belt Driven Installation Guide Rev Page 41 of 54 Figure 35 200 B with Vertical Sump...
Страница 42: ...Waterous 200 B Belt Driven Installation Guide Rev Page 42 of 54 Figure 36 Compressor Dimensions...
Страница 43: ...Waterous 200 B Belt Driven Installation Guide Rev Page 43 of 54 Figure 37 T Sump Dimensions...
Страница 44: ...Waterous 200 B Belt Driven Installation Guide Rev Page 44 of 54 Figure 38 10 Vertical Reservoir...
Страница 45: ...Waterous 200 B Belt Driven Installation Guide Rev Page 45 of 54 Figure 39 Oil Cooler...
Страница 46: ...Waterous 200 B Belt Driven Installation Guide Rev Page 46 of 54 Figure 40 200 B Oil and Separator...
Страница 47: ...Waterous 200 B Belt Driven Installation Guide Rev Page 47 of 54 Figure 41 Separator Bracket...
Страница 48: ...Waterous 200 B Belt Driven Installation Guide Rev Page 48 of 54 Figure 42 Hydraulic Schematic with T Sump...
Страница 50: ...Waterous 200 B Belt Driven Installation Guide Rev Page 50 of 54 Figure 44 Electrical Schematic for Auto sync...