page 4
SOFTENER SYSTEM SETUP
In SOFTENER SYSTEM SETUP you choose the duration for the cycles selected in CYCLE SEQUENCE and specify
other other operating parameters for the system. The upper and lower limits of the allowable values for the cycles are
as follows:
STEP 1S
Step 1S – Press NEXT and simultaneously for 3 seconds and release. If screen in
Step 2S does not appear in 5 seconds the lock on the valve is activated. To unlock press
, NEXT,
∆
, and SET CLOCK in sequence, then press NEXT and
∆
simultaneously for 3
seconds and release.
Step 2S – Choose SOFTENING using the or
∆
button.
Press NEXT to go to Step 3S.
Press REGEN if you want to exit SOFTENER SYSTEM SETUP.
Step 3S – Select the time for the first cycle (which in this example is BACKWASH) using
the or
∆
button.
Press NEXT to go to Step 4S.
Press REGEN if you need to return to previous step.
Step 4S – Select the time for the second cycle (which in this example is dn BRINE) using
the or
∆
button.
Press NEXT to go to Step 5S.
Press REGEN if you need to return to previous step.
NOTE: The display will flash between cycle number and time, and brine direction (dn or
UP).
Step 5S – Select the time for the third cycle (which in this example is RINSE) using the
or
∆
button.
Press NEXT to go to Step 6S.
Press REGEN if you need to return to the previous step.
Step 6S – Select the Lbs. for the fourth cycle (which in this example is FILL) using the
or
∆
button. Press NEXT to go to Step 7S. Press REGEN if you need to return to the
previous step.
Step 7S – Set Grains Capacity using the or
∆
button. The ion exchange capacity is in
grains of hardness as calcium carbonate for the system based on the pounds of salt that
will be used. Calculate the pounds of salt using the fill time previously selected. The
allowable grains capacity range varies from 5000 to 200,000 grains. The increment in-
crease is 500 for the range from 5000 to 30,000, 1000 for the range of 30,000 to 100,000,
and 2000 for the range of 100,000 to 200,000. Grains capacity is affected by the fill time.
The grains capacity for the selected fill time should be confirmed by testing. The capacity
and hardness levels entered are used to automatically calculate reserve capacity when
gallon capacity is set to AUTO. Press NEXT to go to Step 8S.
Press REGEN if you need to to return to previous step.
STEP 2S
ß
STEP 3S
STEP 4S
STEP 5S
STEP 6S
ß
ß
ßß
ß
STEP 7S
ß
Since no time is associated with the END
cycle, the END cycle will not appear in the
SOFTENER SYSTEM SETUP sequence.
Note: Fill is in pounds of salt.
CYCLE SETTING LIMITS
CYCLE OPTIONS
UNITS
LOWER/UPPER LIMIT DEFAULT
Backwash
minutes
1 to 1200
8
Rinse (fast rinse)
6
dn Brine (brine and slow rinse)
6 0
UP Brine (brine and slow rinse)
6 0
Fill (regenerant tank refill)
Lbs.
0.1 to 120.0
6 . 0
Service
minutes
1 to 1200
2 4 0