Troubleshooting - Error Codes
34
Error Code
Error Type
Cause
Reset and Recovery
0
Cam Sense
Error
The valve drive took longer
than 6 minutes to advance
to the next regeneration
position
Unplug the unit and examine the powerhead.Verify
that all cam switches are connected to the circuit
board and functioning properly. Verify that the motor
and drive train components are in good condition
and assembled properly. Check the valve and verify
that the piston travels freely. Replace/reassemble the
various components as necessary.
Plug the unit back in and observe its behavior. The
unit should cycle to the next valve position and stop.
If the error re-occurs, unplug the unit and contact
technical support.
1
Cycle Step Error
The control experienced an
unexpected cycle input
Unplug the unit and examine the powerhead.
Verify that all cam switches are connected to the
circuit board and functioning properly. Enter Master
Programming mode and verify that the valve type
and system type are set correctly with regard to the
unit itself.
Step the unit through a manual regeneration and
verify that it functions correctly. If the error re-occurs
unplug the unit and contact technical support.
2
Regen Failure
The system has not
regenerated for more than 99
days (or 7 days if the Control
Type has been set to Day-of-
Week)
Perform a Manual Regeneration to reset the error
code.
If the system is metered, verify that it is measuring flow
by running service water and watching for the flow
indicator on the display. If the unit does not measure
flow, verify that the meter cable is connected
properly and that the meter is functioning properly.
Enter a Master Programming Mode and verify that
the unit is configured properly. As appropriate for the
valve configuration, check that the correct system
capacity has been selected, that the day override is
set properly, and that meter is identified correctly. If
the unit is configured as a Day-of-Week system, verify
that at least one day is set ON. Correct the settings as
necessary.
3
Memory Error
Control board memory failure Perform a Master Reset and reconfigure the system
via Master Programming Mode. After reconfiguring
the system, step the valve through a manual
regeneration. If the error re-occurs unplug the unit
and contact technical support.
Error Codes
Note: Error codes appear on the In Service display.
Содержание 6200 SXT
Страница 1: ...6200 SXT Upflow Control Valve for Water Conditioning and Treatment Purposes Service Manual...
Страница 21: ...Wiring Diagram 21...
Страница 22: ...6200SXT Upflow Brining Rates 22 6200SXT Upflow Brining Rates with Water 20 PSI Regulated Cap...
Страница 29: ...29 6200 SXT Valve Dimensional Drawings All dimensions are in Inches mm...
Страница 35: ...35...