WATERAX
STRIKER-2/3 Owner's Manual
12
09/2015
Cold Weather Operation
The pump can be run in below freezing temperatures if certain precautions are taken to
avoid the formation of ice in the pump.
1. After priming the pump, the unit should be run at low speed for a short period of time to
allow all components to warm up before continuing with the remaining operating
procedures.
2. Unless wrapped in a heater, drain the pump of all water if it is stopped for any length of
time. The engine/drive unit should be turned over a few revolutions to make sure all
water has been removed from the pump. Drain the pump priming line if a primer has
been used.
3. After use, drain the pump, manifolds, and lines of all water. You can also pour some
antifreeze into the pump and circulate it through the pump and plumbing system.
Basic Care and Storage
The basic care described in this section does not require any disassembly of the pump.
For any servicing procedures that require removing any part of the pump to access a
component, please see the Service section.
WARNING:
Before doing any maintenance to the pump, always ensure that the
equipment cannot be accidentally started. Follow any apparatus and/or departmental
procedures or guidelines in regards to locking out the equipment.
Regular maintenance
After each use:
1. Visually inspect the pump unit.
2. Make sure the mechanical rotary seal is not leaking.
3. Check the pump for external leaks.
4. Check the engine for leaks.
5. Check the condition of the flexible buffer coupling. Replace if worn. See instructions for
removing the pump end from the engine using the quick release pump clamp.
6. Clean any dirt or debris from the pump unit. If necessary, a mild soap and water
solution can be used.
7. Note and report any performance irregularities or any abnormal mechanical sounds.
8. Check all fluid levels and add as needed.
9. Make sure all necessary tools, spares, and accessories are with the pump.
Long-term storage
1. Completely drain the pump of all water.
2. Drain the carburetor. The engine can be run with the fuel valve lever in the OFF
position to drain the system.
3. Drain the fuel tank.
4. Close all valves and plug all openings.
5. Follow any other products, components, apparatus, and departmental procedures
and/or guidelines before placing the unit in storage.
Содержание STRIKER-2/3
Страница 1: ...STRIKER 2 3 Owner s Manual Publication Date 09 2015 Publication Number 701223 Rev 3...
Страница 28: ...WATERAX STRIKER 2 3 Owner s Manual 26 09 2015 Notes...
Страница 29: ...WATERAX STRIKER 2 3 Owner s Manual 09 2015 27...
Страница 30: ...WATERAX STRIKER 2 3 Owner s Manual 28 09 2015...