Wärtsilä JOVYTEC PMS 6000  BAX 2935_en                                                       

- 6 - 

 

N O T E! 

 

The UPS should be attached to the mains supply and switched on at the latest 4 

weeks after receipt in order to prevent the battery discharging itself. 

 

 

P L E A S E   N O T E

 

In order to exclude the possibility of overloading or constant switching over to bypass 

due  to  consumer  generated  non-sinusoidal  current  peaks,  no  devices  such  as  laser 

printers, fax machines as well as devices operating with a similar technology should be 

connected to the UPS. 

In  cases  where  it  is  essential  that  such  devices  be  operated  then  a  UPS  must  be 

selected whose capacity can match the maximum possible current peaks. 

Devices  with  power  reduction  due  to  half  wave  power  consumption,  (e.g.  coffee 

machines, hair dryers) can lead to immediate destruction of the power-output stage. The 

battery is not galvanically isolated from the mains so occurrence of a mains voltage at 

the battery terminals is possible! The UPS unit does not have an output transformer and 

is therefore not galvanically isolated from the mains!! 

 

P L E A S E   N O T E! 

The batteries used are just designed for the required backup time to meet the 

nominal load of the UPS. Operation of the UPS unit in free running mode for a 

longer period of time on battery can damage the batteries. This effect is due to 

the  nature  of  the  battery  since  for  a  longer  discharge  period  the  final 

discharging voltage is not reached. 

 

1.   

General notes 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The device may only be opened by trained specialists. 

 

The system is to be connected up and earthed according to VDE regulations. Provisions of the local energy 

– supply company must be observed. 

 

The ventilation slits on the front and rear sides must not be covered and a distance from the wall of at least 

100 mm

 is essential. 

 

The UPS unit is built according to Protection Class 

IP 21

 and is designed for installation in heated internal 

spaces (at 20°C). A lower operating temperature lowers the bridging time. 

 

No devices with a connecting cable in excess of 

10 metres

 in length should be connected to the UPS. This 

measure serves to ensure observance of the EMC standard. 

 

No alterations should be made to the UPS unit. The warranty will expire in cases of inappropriate physical 

interventions. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.   

Description of the System 

 

Power supply devices of the JOVYATLAS POWERMASTER S – series are particularly suited for supplying 

important  power  consumers  in  industry  and  the  office  such  as  personal  computer,  computer-controlled 

devices,  PLCs  and  similar  equipment.  The  output  voltage  is  sinusoidal.  In  normal  cases  the  attached 

consumers are supplied with power from the installed rectifier and installed inverter from the mains power 

supply  network  (online  operation).  Any  disturbances  in  the  mains  such  as  voltage  peaks,  voltage  drops, 

harmonic distortions or noises etc. are filtered out. The installed battery is constantly being charged up by 

means of a charging rectifier with a charge preservation charging stage which is gentle on the batteries. 

Содержание JOVYTEC POWERMASTER PMS 6000

Страница 1: ...l un I Jet _________ __ Jovyatlas Jovytec PMS 6000 https www uni jet com catalog istochniki besperebojnogo pitaniya on line ibp 1 kva 10kva jovytec pms 6000 html...

Страница 2: ...Operating Manual W rtsil JOVYTEC PMS 6000 BAX 2935 E...

Страница 3: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 2 Index Date Name Revision 0 08 04 2009 Technik Original 1 2015 07 22 Chr Fechteler 15 381 2 3 4 5 6 7 8 9 10...

Страница 4: ...source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating manual without having to make an ann...

Страница 5: ...15 5 6 2 POWERMASTER S 6000 MOUNTED IN 19 CABINET 16 5 6 3 POWERMASTER S 6000 AS TABLE DEVICE 17 6 ELECTRICAL CONNECTION 18 6 1 ELECTRICAL CONNECTION OF THE UPS UNIT 18 6 2 ELECTRICAL CONNECTION OF UP...

Страница 6: ...R 29 9 2 ASSIGNMENT OF THE RS232 INTERFACE 30 9 3 USB PORT OPTIONAL 30 10 SPECIAL EQUIPMENT 30 10 1 ELECTRONIC STOP FUNCTION 30 10 2 UPS INTERNAL MANUAL BYPASS SERVICE BYPASS 31 11 VOLT FREE MESSAGES...

Страница 7: ...rging voltage is not reached 1 General notes The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE regulations Provisions of the local ener...

Страница 8: ...During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating voltage...

Страница 9: ...ns that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault in th...

Страница 10: ...est Factor 3 1 Efficiency AC to AC 88 98 according to the operating mode Switch over behaviour Power failure 0 ms Overload switching Automatic overload switching by the UPS unit Noise level At an appr...

Страница 11: ...5 27 5 623 26 5 7 622 572 ON LI NE ON BAT BYPASS FAULT ON ENTER ESCAPE FUNC O N OF F STATUS 9 5 8 5 483 130 7 469 90 26 5 27 5 27 5 25 428 Graphic 2 Dimensions UPS Graphic 1 Dimensions Battery Pack 5...

Страница 12: ...nting Graphic 3 Dimensions Battery Pack Floor Mounting 572 ON L IN E ON BAT BYPASS FA ULT ON ENTER ESC APE FUNC ON OFF STATUS 8 5 25 428 130 428 130 428 428 572 9 5 25 431 240 431 240 28 28 130 606 5...

Страница 13: ...Battery Pack Wall Mounting 572 ON L INE ON B AT BYPASS FAULT ON EN TER ESC APE FUN C ON OFF STATUS 8 5 25 428 428 130 428 570 5 428 572 9 5 25 585 130 585 130 130 130 130 130 130 130 130 78 5 78 5 78...

Страница 14: ...13 14 15 16 Position Designation 1 Ventilation Inlet 2 Display Indicator 3 Terminal Board 4 USB Port optional 5 Interface for external Display optional 6 Retaining and Fastening Bracket 7 Fan 8 Rack...

Страница 15: ...ERPACK S 6000 1 Graphic 9 Front View POWERPACK S 6000 3 2 Graphic 10 Rear View POWERPACK S 6000 4 Position Designation 1 Cover Plate left and right dismantleable 2 Mounting and Retaining Bracket for 1...

Страница 16: ...rtsil JOVYTEC PMS 6000 BAX 2935_en 15 5 6 Installationsoptions for JOVYATLAS POWERMASTER S 6000 5 6 1 Powermaster S 6000 for verticale or for wall mounting Upright ground mounting Upright wall mountin...

Страница 17: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 16 5 6 2 Powermaster S 6000 mounted in 19 Cabinet...

Страница 18: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 17 5 6 3 Powermaster S 6000 as Table Device...

Страница 19: ...L N J L N OFF 0 OFF 0 OFF 0 OFF 0 PE PE PE Ausgangssicherung Eingangssicherung F1 F2 INPUT FUSE OUTPUT FUSE P L E A S E N O T E Only trained personnel are allowed to work on the UPS unit Observe all...

Страница 20: ...reseen cut outs 4 Connect the input cable to the terminals with the designation input L1 N PE 5 Make sure that there is a wire connection between the terminals J and L at the terminal rail bypass 6 Co...

Страница 21: ...ion between the terminals J and L at the terminal rail bypass have been removed 6 Connect the bypass feeding to terminal rail byass L1 N PE Take care that you don t exchange the L with N 7 Connect the...

Страница 22: ...ONLINE will light up After self test the message LINE MODE will be shown on display The consumers can now be connected Please contact us if anything different happens P L E A S E N OT E The unit shoul...

Страница 23: ...l consumers Press the ON OFF button in the front panel for 5 seconds An acoustic sound bleep is emitted while pressing the ON OFF button and the message Switching off soon appears in the display and t...

Страница 24: ...in allows one to manoeuvre through the parameters If the next parameter is not selected within 10 seconds then the UPS unit indicates its condition again 4 FUNC button The FUNC button can be used to s...

Страница 25: ...an acoustic signal is emitted Press any key in the function panel and the alarm will be switched off The cause of the alarm is shown in the display 7 2 Parameters of the UPS unit Indicator Function o...

Страница 26: ...n Mode Free Run Mode If activated the UPS will switch to bypass if the preset parameters are not maintained ON OFF OFF Operating mode setting HE mode setting Online Offline mode ON OFF OFF Setting for...

Страница 27: ...ttings were adopted in that the display shows High Efficiency The UPS unit will start again automatically after restoration of the mains power and starts in the preset mode after a long period of powe...

Страница 28: ...y window Result The UPS unit will not switch to bypass not activated since the preset parameter has not been maintained and the bypass is deactivated 7 7 5 Free running ON bypass activated Example Inp...

Страница 29: ...essary The UPS switches again to normal operation after a successful battery test Overcharging over charge Continuous tone The batteries are over charged Battery charge voltage too high Contact the se...

Страница 30: ...via the network or the internet or an AS 400 card with voltage free contacts The RS 232 and USB interfaces serve to allow data transmission between a computer and the UPS unit The UPS unit can be mon...

Страница 31: ...delivered as standard and the optionally obtainable JUMP software 10 Special equipment 10 1 Electronic STOP function The UPS is fitted with an integrated electronic STOP function This function is dea...

Страница 32: ...UPS Move switch internal manual bypass to bypass Now the ups has been separated from mains and the UPS can be switched of by pushing the ON OFF button To switch back the ups to normal operation the pr...

Страница 33: ...UPS unit to be switched voltage free and the UPS unit shuts down In order to supply consumers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be restar...

Страница 34: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 33...

Страница 35: ...rter switches off automatically and the consumers are no longer supplied with power When the mains power is restored the consumers begin again to be supplied with power via the inverter The inverter i...

Страница 36: ...ing life of batteries 10 12 years 6 9 years 3 5 years Temperature Expected working life of batteries 20 C 12 years 9 years 5 years 30 C 5 years 4 years 2 5 years 40 C 2 5 years 2 years 1 25 years 12 4...

Страница 37: ...c voltage inside the battery pack so only qualified personel is allowed to exchange the battery 4 Screw the battery pack together again using the cross head screws 5 Push the battery pack into the bat...

Страница 38: ...________________________________________________________________________________ ______________________________________________________________________________________ ________________________________...

Отзывы: