N O T E S !

 

 

Notes concerning this operating manual 

 

Thank  you  for  deciding  to  purchase  this  uninterrupted  power  supply  unit  (UPS)  model  JOVYATLAS  POWERMASTER  S  6000.  It 

represents reliable protection for the attached consumers. 

 

Please read through this manual very carefully 

 

This manual contains regulations covering safety, installation and operating methods which will help you  guarantee to obtain the full 

performance und operational readiness which the UPS can offer. 

 

Put this manual in a place of safe keeping  

 

It contains important regulations for safe use of this UPS and for reaching manufacturer services if, for some reason, correct operation 

of the UPS is in doubt. 

 

Keep or reuse the packaging material 

 

The packaging material for the UPS was designed with great care to protect its contents against damage during transport. This material 

is also useful if you ever have to send the UPS back for checking. Damage which occurs during transport is not covered by the warranty 

provisions. 

 

Duty to instruct persons 

 

This operating manual is to be read through carefully before assembly and first use of the UPS by persons who will be working with or 

on the UPS. 

 

This operating manual is an integral part of the UPS. The operator of this device is required to make this operating manual available in 

an unlimited fashion to every group of persons who transport the UPS, commission it, maintain it or who do any other kind of work on 

this device. 

 

Validity 

 

This operating manual is in line with state-of-the-art UPS technology at its time of publishing. The contents are not part of the  contract 

but simply serve as a source of information. 

 

Wärtsilä  JOVYATLAS  EUROATLAS  GmbH  reserves  the  right  to  make  any  necessary  changes  to  the  contents  and  technology 

described in this operating manual without having to make an announcement to this effect. Wärtsilä JOVYATLAS EUROATLAS GmbH 

cannot be held responsible for any errors or improper information in this operating manual since there is no duty upon the company to 

update this operating manual on an ongoing basis. 

 

Loss of warranty 

 

Our deliveries and services rendered are subject to the General Delivery Conditions for Products of the Electrical Industry as well as  

our  General  Sales  Conditions. We  reserve  full  rights  to make  any  changes  to  this  operating manual,  in  particular  to  technical  data, 

operation, dimensions and weights. We request that you make any claims concerning delivered goods within eight days after arrival of 

the goods together with the packing slip. Complaints made later than this cannot be considered. 

 

JOVYATLAS

 GmbH will annul all duties upon 

JOVYATLAS

 GmbH and its dealers such as promises to offer a warranty period, service 

contracts etc. without warning if any spare parts other than original parts are used for maintenance and repair purposes. 

 

Handling 

 

This operating manual for the UPS is constructed in such a way that all work required for commissioning, maintenance and repair can 

be conducted by appropriate skilled personnel. 

 

The Service Hotline 

 

There  is  further  information  available  under  chapter  8  “

Service  information

“for  questions  about  the  UPS  unit,  about  the  operating 

manual, service etc. 

 

Copyright 

 

Any passing on, duplication and/or transfer by means of electronic or mechanical means, also extracts thereof, of this operating manual, 

requires express prior written permission from Wärtsilä JOVYATLAS EUROATLAS GmbH. 

 

Copyright Wärtsilä JOVYATLAS EUROATLAS GmbH 2015. All rights reserved. 

Содержание JOVYTEC POWERMASTER PMS 6000

Страница 1: ...l un I Jet _________ __ Jovyatlas Jovytec PMS 6000 https www uni jet com catalog istochniki besperebojnogo pitaniya on line ibp 1 kva 10kva jovytec pms 6000 html...

Страница 2: ...Operating Manual W rtsil JOVYTEC PMS 6000 BAX 2935 E...

Страница 3: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 2 Index Date Name Revision 0 08 04 2009 Technik Original 1 2015 07 22 Chr Fechteler 15 381 2 3 4 5 6 7 8 9 10...

Страница 4: ...source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating manual without having to make an ann...

Страница 5: ...15 5 6 2 POWERMASTER S 6000 MOUNTED IN 19 CABINET 16 5 6 3 POWERMASTER S 6000 AS TABLE DEVICE 17 6 ELECTRICAL CONNECTION 18 6 1 ELECTRICAL CONNECTION OF THE UPS UNIT 18 6 2 ELECTRICAL CONNECTION OF UP...

Страница 6: ...R 29 9 2 ASSIGNMENT OF THE RS232 INTERFACE 30 9 3 USB PORT OPTIONAL 30 10 SPECIAL EQUIPMENT 30 10 1 ELECTRONIC STOP FUNCTION 30 10 2 UPS INTERNAL MANUAL BYPASS SERVICE BYPASS 31 11 VOLT FREE MESSAGES...

Страница 7: ...rging voltage is not reached 1 General notes The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE regulations Provisions of the local ener...

Страница 8: ...During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating voltage...

Страница 9: ...ns that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault in th...

Страница 10: ...est Factor 3 1 Efficiency AC to AC 88 98 according to the operating mode Switch over behaviour Power failure 0 ms Overload switching Automatic overload switching by the UPS unit Noise level At an appr...

Страница 11: ...5 27 5 623 26 5 7 622 572 ON LI NE ON BAT BYPASS FAULT ON ENTER ESCAPE FUNC O N OF F STATUS 9 5 8 5 483 130 7 469 90 26 5 27 5 27 5 25 428 Graphic 2 Dimensions UPS Graphic 1 Dimensions Battery Pack 5...

Страница 12: ...nting Graphic 3 Dimensions Battery Pack Floor Mounting 572 ON L IN E ON BAT BYPASS FA ULT ON ENTER ESC APE FUNC ON OFF STATUS 8 5 25 428 130 428 130 428 428 572 9 5 25 431 240 431 240 28 28 130 606 5...

Страница 13: ...Battery Pack Wall Mounting 572 ON L INE ON B AT BYPASS FAULT ON EN TER ESC APE FUN C ON OFF STATUS 8 5 25 428 428 130 428 570 5 428 572 9 5 25 585 130 585 130 130 130 130 130 130 130 130 78 5 78 5 78...

Страница 14: ...13 14 15 16 Position Designation 1 Ventilation Inlet 2 Display Indicator 3 Terminal Board 4 USB Port optional 5 Interface for external Display optional 6 Retaining and Fastening Bracket 7 Fan 8 Rack...

Страница 15: ...ERPACK S 6000 1 Graphic 9 Front View POWERPACK S 6000 3 2 Graphic 10 Rear View POWERPACK S 6000 4 Position Designation 1 Cover Plate left and right dismantleable 2 Mounting and Retaining Bracket for 1...

Страница 16: ...rtsil JOVYTEC PMS 6000 BAX 2935_en 15 5 6 Installationsoptions for JOVYATLAS POWERMASTER S 6000 5 6 1 Powermaster S 6000 for verticale or for wall mounting Upright ground mounting Upright wall mountin...

Страница 17: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 16 5 6 2 Powermaster S 6000 mounted in 19 Cabinet...

Страница 18: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 17 5 6 3 Powermaster S 6000 as Table Device...

Страница 19: ...L N J L N OFF 0 OFF 0 OFF 0 OFF 0 PE PE PE Ausgangssicherung Eingangssicherung F1 F2 INPUT FUSE OUTPUT FUSE P L E A S E N O T E Only trained personnel are allowed to work on the UPS unit Observe all...

Страница 20: ...reseen cut outs 4 Connect the input cable to the terminals with the designation input L1 N PE 5 Make sure that there is a wire connection between the terminals J and L at the terminal rail bypass 6 Co...

Страница 21: ...ion between the terminals J and L at the terminal rail bypass have been removed 6 Connect the bypass feeding to terminal rail byass L1 N PE Take care that you don t exchange the L with N 7 Connect the...

Страница 22: ...ONLINE will light up After self test the message LINE MODE will be shown on display The consumers can now be connected Please contact us if anything different happens P L E A S E N OT E The unit shoul...

Страница 23: ...l consumers Press the ON OFF button in the front panel for 5 seconds An acoustic sound bleep is emitted while pressing the ON OFF button and the message Switching off soon appears in the display and t...

Страница 24: ...in allows one to manoeuvre through the parameters If the next parameter is not selected within 10 seconds then the UPS unit indicates its condition again 4 FUNC button The FUNC button can be used to s...

Страница 25: ...an acoustic signal is emitted Press any key in the function panel and the alarm will be switched off The cause of the alarm is shown in the display 7 2 Parameters of the UPS unit Indicator Function o...

Страница 26: ...n Mode Free Run Mode If activated the UPS will switch to bypass if the preset parameters are not maintained ON OFF OFF Operating mode setting HE mode setting Online Offline mode ON OFF OFF Setting for...

Страница 27: ...ttings were adopted in that the display shows High Efficiency The UPS unit will start again automatically after restoration of the mains power and starts in the preset mode after a long period of powe...

Страница 28: ...y window Result The UPS unit will not switch to bypass not activated since the preset parameter has not been maintained and the bypass is deactivated 7 7 5 Free running ON bypass activated Example Inp...

Страница 29: ...essary The UPS switches again to normal operation after a successful battery test Overcharging over charge Continuous tone The batteries are over charged Battery charge voltage too high Contact the se...

Страница 30: ...via the network or the internet or an AS 400 card with voltage free contacts The RS 232 and USB interfaces serve to allow data transmission between a computer and the UPS unit The UPS unit can be mon...

Страница 31: ...delivered as standard and the optionally obtainable JUMP software 10 Special equipment 10 1 Electronic STOP function The UPS is fitted with an integrated electronic STOP function This function is dea...

Страница 32: ...UPS Move switch internal manual bypass to bypass Now the ups has been separated from mains and the UPS can be switched of by pushing the ON OFF button To switch back the ups to normal operation the pr...

Страница 33: ...UPS unit to be switched voltage free and the UPS unit shuts down In order to supply consumers with voltage again it is necessary for the electronic STOP switch to be reset and for the UPS to be restar...

Страница 34: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 33...

Страница 35: ...rter switches off automatically and the consumers are no longer supplied with power When the mains power is restored the consumers begin again to be supplied with power via the inverter The inverter i...

Страница 36: ...ing life of batteries 10 12 years 6 9 years 3 5 years Temperature Expected working life of batteries 20 C 12 years 9 years 5 years 30 C 5 years 4 years 2 5 years 40 C 2 5 years 2 years 1 25 years 12 4...

Страница 37: ...c voltage inside the battery pack so only qualified personel is allowed to exchange the battery 4 Screw the battery pack together again using the cross head screws 5 Push the battery pack into the bat...

Страница 38: ...________________________________________________________________________________ ______________________________________________________________________________________ ________________________________...

Отзывы: