Wärtsilä JOVYTEC PMS 6000 BAX 2935_en
- 19 -
L N PE
L
N
PE
L
N
PE
J
RECTIFIER
INVERTER
STATIC BYPASS
L
N
PE
BYPASS
INPUT
F
RECTIFIER
INPUT
=
=
~
~
D02/35A
6.2
Electrical connection of UPS for one mains feeding
1.
Switch off the input- and output switch on rear side of the UPS
2.
Dismantle the cover plate with a Phillips Screw Driver
3.
Guide the leads through the foreseen cut outs
4.
Connect the input cable to the terminals with the designation input L1, N, PE
5.
Make sure that there is a wire connection between the terminals J and L at the terminal rail bypass.
6.
Connect the output cables to the terminals with the designation output L1, N, PE
7.
Fix the cover plate with a Phillips Screw Driver
8.
Switch on the input switch
9.
Connect the battery pack to the battery jack on rear side of the UPS
10.
Switch on the output switch
11.
The electrical connection is herewith already done
Graphic 12: UPS with one mains feeding