- 20 -
L N PE
L
N
PE
L
N
PE
J
RECTIFIER
INVERTER
STATIC BYPASS
L
N
PE
BYPASS
INPUT
F
RECTIFIER
INPUT
=
=
~
~
F
L N PE
D02/35A
D02/35A
6.3
Electrical connection of UPS for two mains feeding
1.
Switch off the input- and output switch on rear side of the UPS
2.
Dismantle the cover plate with a Phillips Screw Driver
3.
Guide the leads through the foreseen cut outs
4.
Connect the input cable to the terminals with the designation input L1, N, PE
5.
Make sure that the wire connection between the terminals J and L at the terminal rail bypass have been
removed.
6.
Connect the bypass feeding to terminal rail byass L1, N, PE. (Take care that you don´t exchange the L with
N)
7.
Connect the output cables to the terminals with the designation output L1, N, PE
8.
Fix the cover plate with a Phillips Screw Driver
9.
Switch on the input switch
10.
Connect the battery pack to the battery jack on rear side of the UPS
11.
Switch on the output switch
12.
The electrical connection is herewith already done
Graphic 13: UPS with two mains feedings
P L E A S E N O T E
!
Both mains feeding must have the same connection.
Don´t exchange L1, N , PE, this will cause a short circuit which will destroy the UPS!!
Содержание JOVYTEC POWERMASTER PMS 6000
Страница 2: ...Operating Manual W rtsil JOVYTEC PMS 6000 BAX 2935 E...
Страница 17: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 16 5 6 2 Powermaster S 6000 mounted in 19 Cabinet...
Страница 18: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 17 5 6 3 Powermaster S 6000 as Table Device...
Страница 34: ...W rtsil JOVYTEC PMS 6000 BAX 2935_en 33...