Wärtsilä JOVYTEC PMS 6000 BAX 2935_en
- 21 -
BYPASS
INPUT
OUTPUT
L
N
L
N
J
L
N
OFF
0
OFF
0
OFF
0
OFF
0
Eingangssicherung
F1
F2
Ausgangssicherung
PE
PE
PE
6.4
Commissioning the UPS unit
Take note:
The unit fans run as soon as the input voltage is applied!!
Make sure that UPS has been installed correctely. The battery pack has to be connected via battery
connector to the battery jack on rear side of the ups. Make sure that the input- and output switch have
been switched on.
Graphic 14: Battery Jack Battery Jack
The UPS can be startet througt pushing the push button ON/OFF for 2 seconds at the front panel of the UPS.
Now the UPS will initialize a self test, which will check the internal functions of the device. The mains
synchronisation and the inverter will be started. During self test the message “READY ON” will be shown on
display and the LED´s “ON” and “ONLINE” will light up. After self test the message “LINE MODE” will be shown
on display. The consumers can now be connected.
Please contact us if anything different happens!
P L E A S E N OT E!
The unit should be started over the input mains. If the input mains is not available for a short
time then it is also possible to start the unit over the external battery. It is a basic prerequisite for
this operating mode that the UPS unit was one time operated over the energy supplier’s mains
network. Please note that when starting over the external battery, the maximum time the output
voltage is available to you is the autonomy time. The UPS unit will also start with the set
parameter, that is if the mains previously had 50 Hz then the UPS will also produce 50 Hz on the
output side
.
P L E A S E N OT E!
The voltage specification on the UPS must match with the voltage specification on the battery
cabinet (DIRECT CURRENT LINK VOLTAGE) otherwise there is danger of destroying internal
components of the UPS or destruction of the battery
.
INPUT FUSE
OUTPUT FUSE
Содержание JOVYTEC POWERMASTER PMS 6000