where:
Preheating time [h]
t =
Engine specific coefficient = 1 kW
k
eng =
Number of cylinders
n
cyl =
P < 3.5 kW/cyl
The formula above should not be used for
Circulation pump for preheater (4P04)
Design data:
0.4 m
3
/h per cylinder
Capacity
80 kPa (0.8 bar)
Delivery pressure
Preheating unit (4N01)
A complete preheating unit can be supplied. The unit comprises:
•
Electric or steam heaters
•
Circulating pump
•
Control cabinet for heaters and pump
•
Set of thermometers
•
Non-return valve
•
Safety valve
Figure 9.8
Preheating unit, electric (3V60L0562C).
Dimensions [mm]
Pipe
conn.
Weight
[kg]
Pump capacity
[m³/h]
Heater capacity
[kW]
E
D
C
B
A
In/outlet
60 HZ
50 Hz
460
240
660
900
1250
DN40
95
13
11
18
480
290
700
720
1050
DN40
100
13
11
22.5
480
290
700
900
1250
DN40
103
13
12
27
480
290
700
720
1050
DN40
105
13
12
30
480
290
700
900
1250
DN40
125
13
12
36
510
350
755
720
1250
DN40
145
13
12
45
510
350
755
900
1250
DN40
150
13
12
54
550
400
805
900
1260
DN40
187
13
12
72
550
400
805
900
1260
DN40
190
13
12
81
96
Product Guide Wärtsilä 34DF - 3/2012
Product Guide