Dimensions [mm]
Pipe
conn.
Weight
[kg]
Pump capacity
[m³/h]
Heater capacity
[kW]
E
D
C
B
A
In/outlet
60 HZ
50 Hz
575
450
855
900
1260
DN40
215
13
12
108
9.3.14
Throttles
Throttles (orifices) are to be installed in all by-pass lines to ensure balanced operating conditions for tem-
perature control valves. Throttles must also be installed wherever it is necessary to balance the waterflow
between alternate flow paths.
9.3.15
Thermometers and pressure gauges
Local thermometers should be installed wherever there is a temperature change, i.e. before and after heat
exchangers etc.
Local pressure gauges should be installed on the suction and discharge side of each pump.
Product Guide Wärtsilä 34DF - 3/2012
97
Product Guide
9. Cooling Water System